Azbil MY8045A Specifications & Instructions Download Page 4

AB-6682 

Specifications 

Item Specification 

Model number 

MY8045A2001 

Power supply voltage 

24 V AC 

±

 20 %, 50 Hz (Do not use this product at 60 Hz utility fequency.) 

Power consumption 

10 VA 

Rotating angle 

Max. 95

°

 

Operating time 

Motor: Approx. 150 s  / Spring-return: Approx. 16 s 

Torque at the rated voltage 

15 N

Ambient operating conditions 

-20 

°

C to 50 

°

C, 10 %RH to 90 %RH (non-condensing) 

Transport/storage conditions 

-20 

°

C to 60 

°

C, 95 %RH or less (non-condensing) 

Enclosure rating 

IEC IP54 (dust-proof and splash-proof) 
* This product is not rain-proof and thus is for indoor use only. 
(Cable conduit must be facing downward.) 

Cable 0.75 

mm

2

 

×

 3 cores, 1 m long 

Color Silver 

gray 

Weight 2800 

Applicable damper shaft 

Circular: 

φ

10 mm to 

φ

20 mm, 95 mm long or longer 

Square: 10 mm diagonal to 16 mm diagonal, 95 mm long or longer 

Accessories 

 M4 tapping screws 

×

 2 

 Universal bracket 

×

 1 (Part No. 12596-0001) 

 Mechanical stopper (Part No. ZDB-AF) 

 Installation instruction sheet 

×

 1 

 Hexagon wrench 

×

 1

 

Insulation resistance 

Between case and cable: 100 M

Ω

 or higher at 500 V DC 

Withstand voltage 

Between case and cable: 500 V AC for 1 min., 1 mA or less 

Control signal 

SAnet 

Communication Transmission 

system 

Voltage transmission (SAnet) 

(via SAnet) 

Transmission speed 

1200 bps 

 Transmission 

distance 

Transmission distance varies depending on the number of devices and the type of devices 
to be connected to.  For details on the transmission distance, refer to 

Installation Manual 

of Intelligent Component Series for SAnet Communication

 (AB-6713). 

 

Function 

Function Description 

Data monitoring*

1

 

Following items can be monitored/operated from the host system (savic-net FX) and  
Infilex GC / Infilex GD. 
Damper position setting, damper position measuring 

Adaption 
(setting of rotation angle) 

Rotation angle of the damper (controlled by the actuator) is adjusted with PC-MMI or with 
Data Setter. (See P.10.) 

Damper position 
adjustment 

Synchronisation*

2

 

(position alignment) 

Actual damper position and the position of the actuator are matched with PC-MMI, with 
Data Setter, or when power is restored from blackout. (See P.10.) 

Notes: 

1  Above functions are available in combination with Infilex GC/Infilex GD and savic-net FX. 

2  Positions of the actuator and of the damper are matched by fully closing the actuator and the damper. 

Synchronisation at the time of power restoration is enabled/disabled by parameter setting.

  

 

Summary of Contents for MY8045A

Page 1: ...ler Manual open close function allows easy adjustment without power supply Torque limit circuit inside the actuator automatically stops the damper in fully closed or open positions Low power consumpti...

Page 2: ...that keeps product operating cycle excessively frequent Overuse of the product may shorten the product service life Installation and wiring must be performed by qualified personnel in accordance with...

Page 3: ...el WY5117C Infilex GC Model WY5111 Infilex GD Model WY5110 PMX III Model WY2001 Infilex FC Model WY5205 Infilex VC Model WY5206 Neopanel Model QY7205 Digital user terminal Neoplate Model QY7290 Analog...

Page 4: ...500 V AC for 1 min 1 mA or less Control signal SAnet Communication Transmission system Voltage transmission SAnet via SAnet Transmission speed 1200 bps Transmission distance Transmission distance var...

Page 5: ...6682 5 Dimensions Actuator Figure 2 Dimensions mm Damper actuator Clearance for maintenance 148 5 248 98 97 5 200 57 50 100 10 188 49 5 1 6 5 Clearance for maintenance 28 12 5 5 67 10 100 188 80 9 10...

Page 6: ...itionally order only when necessary Parts Identification Figure 4 Parts identification 2 pan head tapping screws slotted M4 12 1 4 pitch equivalent to JIS B 1115 1976 are attached to the universal bra...

Page 7: ...of the actuator and fix the bracket onto the damper with the two M4 tapping screws Figure 6 Installation of the actuator with forward rotation to min 95 mm long shaft 2 3 Confirm that the damper shaf...

Page 8: ...R side outward Figure 10 Installation of the actuator with reverse rotation to 20 95 mm long shaft Wiring CAUTION To prevent product damage always disconnect the power supply from the product before p...

Page 9: ...SAnet ID on the SAnet ID label and address number to set The SAnet ID label is attached on a side surface of the actuator as shown in Fig 12 Figure 12 Locations of the labels IMPORTANT Address settin...

Page 10: ...actuator and the actual damper position agree synchronize Note that Synchronisation is performed by our service personnel To our service personnel Refer to Engineering Manual of Intelligent Component...

Page 11: ...haft Insert the accessory hexagon wrench to the hexagonal hole provided on the front surface of the damper actuator Rotate the wrench to open direction until the lock is released Once the lock is rele...

Page 12: ...AB 6682 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 1 1 Jul 2012 AB 6682 J AI 6682 Rev 1 0 12...