AB-6682
4
Specifications
Item Specification
Model number
MY8045A2001
Power supply voltage
24 V AC
±
20 %, 50 Hz (Do not use this product at 60 Hz utility fequency.)
Power consumption
10 VA
Rotating angle
Max. 95
°
Operating time
Motor: Approx. 150 s / Spring-return: Approx. 16 s
Torque at the rated voltage
15 N
⋅
m
Ambient operating conditions
-20
°
C to 50
°
C, 10 %RH to 90 %RH (non-condensing)
Transport/storage conditions
-20
°
C to 60
°
C, 95 %RH or less (non-condensing)
Enclosure rating
IEC IP54 (dust-proof and splash-proof)
* This product is not rain-proof and thus is for indoor use only.
(Cable conduit must be facing downward.)
Cable 0.75
mm
2
×
3 cores, 1 m long
Color Silver
gray
Weight 2800
g
Applicable damper shaft
Circular:
φ
10 mm to
φ
20 mm, 95 mm long or longer
Square: 10 mm diagonal to 16 mm diagonal, 95 mm long or longer
Accessories
•
M4 tapping screws
×
2
•
Universal bracket
×
1 (Part No. 12596-0001)
•
Mechanical stopper (Part No. ZDB-AF)
•
Installation instruction sheet
×
1
•
Hexagon wrench
×
1
Insulation resistance
Between case and cable: 100 M
Ω
or higher at 500 V DC
Withstand voltage
Between case and cable: 500 V AC for 1 min., 1 mA or less
Control signal
SAnet
Communication Transmission
system
Voltage transmission (SAnet)
(via SAnet)
Transmission speed
1200 bps
Transmission
distance
Transmission distance varies depending on the number of devices and the type of devices
to be connected to. For details on the transmission distance, refer to
Installation Manual
of Intelligent Component Series for SAnet Communication
(AB-6713).
Function
Function Description
Data monitoring*
1
Following items can be monitored/operated from the host system (savic-net FX) and
Infilex GC / Infilex GD.
Damper position setting, damper position measuring
Adaption
(setting of rotation angle)
Rotation angle of the damper (controlled by the actuator) is adjusted with PC-MMI or with
Data Setter. (See P.10.)
Damper position
adjustment
Synchronisation*
2
(position alignment)
Actual damper position and the position of the actuator are matched with PC-MMI, with
Data Setter, or when power is restored from blackout. (See P.10.)
Notes:
∗
1 Above functions are available in combination with Infilex GC/Infilex GD and savic-net FX.
∗
2 Positions of the actuator and of the damper are matched by fully closing the actuator and the damper.
Synchronisation at the time of power restoration is enabled/disabled by parameter setting.