Azbil Infilex BC WY5610 Specifications & Instructions Download Page 11

AB-7163 

11 

Wiring 

Wiring to the power supply terminals 

Crimp the M3 terminal lugs to the wire ends, and connect 
them to the M3 screw terminals. 

 

Wiring to I/O modules and expansion bus terminals 

Since screwless push-in terminals are adopted for the I/O 
modules and the expansion bus terminals, the procedure for 
connection is specified as follows. 

1)  Strip the wire sheath 8 mm. (The gauge for the strip 

length is located at the front lower part of Infilex BC I/O 
control unit.  If the stripped part is longer than 8 mm, the 
conductor will be exposed, causing electrical shock or 
short circuit between adjacent terminals.  If it is shorter, 
the conductor may not contact the connector.) 

2)  Make sure that no wire fiber is protruded from the 

conductor (stripped wire). 

3)  Press the clamp release button on the terminals deeply 

enough to insert the wire using a slotted screwdriver. 
(Maximum button-pressing force is 14 N.) 

4)  Release the button, and gently pull out the wire 

horizontally to make sure that it is tightly fastened. (If you 
pull out the wire diagonally, it may be disconnected.) 
Make sure that no wire fiber is protruded from the 
conductor (stripped conductor). 

 

Positions for connected wires 

Neatly place the wires, using cable ties or the like,  connected 
to Infilex BC I/O control unit so as not to hide LED, Data 
Setter connector, 

 mark, S1 switch, battery holder, or 

indication tag, as shown in Fig. 8.   
Make sure there is no slack in the wires from the cable ducts 
to Infilex BC I/O control unit. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 8.  Connected wires in position (example) 

Tube marker 

Since Infilex BC I/O control unit adopts a screwless push-in 
terminals, wires are connected without crimp terminals.  
Therefore, if normal tube markers are used, they may come 
off when the wires are disconnected.  To prevent this, use the 
following Flat Tube Marker.  It is held on a wire by friction and 
thus does not come off easily. 

Manufacturer 

Phoenix Contact  

Part name 

Flat Tube Marker 

Part number 

5880029 

Model TMC-3 
Applicable wire size 

0.4 mm

2

 to 2 mm

2

 

Package unit 

200 m/roll 

 

System indication label for the controller number 

The indication tag has the system indication label on its back. 
Turn it over and fill in the controller number on the label. 

 

 

 

 

 

 

 

 

 

 

 

Figure 9.  System indication label 

 

Protective sheet 

After connecting the wires, be sure to peel off the protective 
sheet before turning on the power. 

1)  Adhesive is applied to the sheet approximately 20 mm 

from the front edge.  Peel off this area. 

2)  Tear off the sheet along the perforations. 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 10.  Protective sheet 

 

2) Tear off. 

1) Peel off the adhesive area. 

Indication tag 

Turn over.

S1 switch 

 
Connector for 
Data Setter 

LED 

Power switch 

 

LED 

 

Battery holder 

Indication tag 

Summary of Contents for Infilex BC WY5610

Page 1: ...ler Infilex BC is integrated in the BACnet IP network Compact design Small size body allows free installation in a desired place I O module configurations Input and output types are selectable and the...

Page 2: ...wiring be sure to turn off the power to the product Failure to do so might cause electric shock Be sure to ground the product with ground resistance of less than 100 Improper grounding might cause el...

Page 3: ...will not contact the connector Do not block the ventilation holes of this product Be sure to peel off the protective sheet after installation and wiring Doing so might cause fire or device failure Af...

Page 4: ...dition to the I O modules UT module and or integral type Operator Panel may be connected Figure 2 System configuration example Infilex BC Models WY5610W0000 and WY5611W0000 integrated into savic net F...

Page 5: ...RY50XX Order Number of Infilex BC Model WY5610W0010 control unit and Model WY5611W0000 I O control unit Order number Description 83171682 Infilex BC 101 One control unit and one I O control unit 103 O...

Page 6: ...M3 screw terminals 7 62 mm pitch between terminals Terminals connection Expansion bus communication Screwless push in terminals Wiring specifications I O control unit Item Wiring Wiring length Condit...

Page 7: ...This product complies with the following Electromagnetic Compatibility EMC and the Low Voltage Directive LVD EMC EN61326 1 Class A Table 2 For use in an industrial electromagnetic environment LVD EN61...

Page 8: ...AB 7163 8 Dimensions Figure 4 Dimensions mm 60 90 140...

Page 9: ...ex BC I O control unit At this time hold the male connector with the mark facing left and insert it as the mark points to the mark on the Infilex BC I O control unit Connection of Data Setter Model QY...

Page 10: ...ilex BC I O control unit with the modules varies depending on the number of the modules I O modules UT module and or integral type Operator Panel to be assembled Width of Infilex BC I O control unit O...

Page 11: ...ike connected to Infilex BC I O control unit so as not to hide LED Data Setter connector mark S1 switch battery holder or indication tag as shown in Fig 8 Make sure there is no slack in the wires from...

Page 12: ...oduct is always in use in ON state Replace the lithium battery with the power ON If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product...

Page 13: ...eral tens of seconds are required for the product normal operation after the power is turned on During this time the red LED ERR1 major failure on the front lights up indicating major failure temporar...

Page 14: ...AB 7163 14 Blank page added for editing purpose...

Page 15: ...AB 7163 15 Blank page added for editing purpose...

Page 16: ...t is a registered trademark of American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE KPEV is a registered trademark of Furukawa Electric Co Ltd in Japan Specifications are su...

Reviews: