Azbil Infilex BC WY5610 Specifications & Instructions Download Page 10

AB-7163 

10 

Mounting Dimensions 

The following figure shows the mounting dimensions of Infilex BC I/O control unit assembled with the modules (I/O modules, UT 
module, and/or integral type Operator Panel) on the DIN rail. 
Mount and fix Infilex BC I/O control unit assembled with the modules onto the DIN rail so that they do not fall from the DIN rail.  
Check that the DIN rail holders of each module are pushed up and fixed on the DIN rail. 
Fasten the bilateral sides of Infilex BC I/O control unit assembled with the modules with two DIN rail mounting brackets (Part No. 
83104567-001, optional). 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes: 

1  Pitch between upper/lower duct and DIN rail. 

2  Hatched area shows the maintenance space. 

3  ‘n’ indicates the number of I/O module, UT module, and/or integral type Operator Panel assembled with Infilex BC I/O control unit. 

4  DIN rail position is shifted 5 mm downward from the center of Infilex BC I/O control unit. 

 

The width of Infilex BC I/O control unit with the modules varies depending on the number 
of the modules (I/O modules, UT module, and/or integral type Operator Panel) to be 
assembled.  

Width of Infilex BC I/O control unit  
= One module (30 mm) 

 n (quantity) + Infilex BC I/O control unit (60 mm) 

 
Notes: 

  Panel mount type Operator Panel is not directly assembled with Infilex BC I/O control unit.  To 

connect it to Infilex BC, a UT module is required. 
For details of panel mount type Operator Panel, please refer to 

Specifications/Instructions of 

Model RY5001Q/QY5100W (AB-6546)

  For details of I/O modules, UT module, and integral type Operator Panel that can be assembled 

with Infilex BC I/O control unit, refer to 

Specifications/Instructions of Model RY50XX 

(AB-6527)

 

 

 

 

 

 

 

 

 

 

 

 

I/O module (mm) 

 

Figure 7.  Mounting dimensions: DIN rail mounting (mm) 

 

 

 

DIN rail mounting brackets for bilateral sides
Part No. 83104567-001

 

Duct

Duct

Infilex BC 

I/O control unit

(45

)    3

140 

(45) 

(122.5)*

1

 

           (132.

5)*

1

 

Duct 

20

50 

92

(60)

(60)

Duct 

65 75 

35 

2

DIN rail holder 

Infilex BC 

I/O control  

unit

DIN rail 

Infilex BC 
I/O control 
unit 

60 + 30 

 n*

3

 

Hook 

I/O modules, UT 

module, integral type 

Operator Panel 

5*

4

 

106

30 

Summary of Contents for Infilex BC WY5610

Page 1: ...ler Infilex BC is integrated in the BACnet IP network Compact design Small size body allows free installation in a desired place I O module configurations Input and output types are selectable and the...

Page 2: ...wiring be sure to turn off the power to the product Failure to do so might cause electric shock Be sure to ground the product with ground resistance of less than 100 Improper grounding might cause el...

Page 3: ...will not contact the connector Do not block the ventilation holes of this product Be sure to peel off the protective sheet after installation and wiring Doing so might cause fire or device failure Af...

Page 4: ...dition to the I O modules UT module and or integral type Operator Panel may be connected Figure 2 System configuration example Infilex BC Models WY5610W0000 and WY5611W0000 integrated into savic net F...

Page 5: ...RY50XX Order Number of Infilex BC Model WY5610W0010 control unit and Model WY5611W0000 I O control unit Order number Description 83171682 Infilex BC 101 One control unit and one I O control unit 103 O...

Page 6: ...M3 screw terminals 7 62 mm pitch between terminals Terminals connection Expansion bus communication Screwless push in terminals Wiring specifications I O control unit Item Wiring Wiring length Condit...

Page 7: ...This product complies with the following Electromagnetic Compatibility EMC and the Low Voltage Directive LVD EMC EN61326 1 Class A Table 2 For use in an industrial electromagnetic environment LVD EN61...

Page 8: ...AB 7163 8 Dimensions Figure 4 Dimensions mm 60 90 140...

Page 9: ...ex BC I O control unit At this time hold the male connector with the mark facing left and insert it as the mark points to the mark on the Infilex BC I O control unit Connection of Data Setter Model QY...

Page 10: ...ilex BC I O control unit with the modules varies depending on the number of the modules I O modules UT module and or integral type Operator Panel to be assembled Width of Infilex BC I O control unit O...

Page 11: ...ike connected to Infilex BC I O control unit so as not to hide LED Data Setter connector mark S1 switch battery holder or indication tag as shown in Fig 8 Make sure there is no slack in the wires from...

Page 12: ...oduct is always in use in ON state Replace the lithium battery with the power ON If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product...

Page 13: ...eral tens of seconds are required for the product normal operation after the power is turned on During this time the red LED ERR1 major failure on the front lights up indicating major failure temporar...

Page 14: ...AB 7163 14 Blank page added for editing purpose...

Page 15: ...AB 7163 15 Blank page added for editing purpose...

Page 16: ...t is a registered trademark of American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE KPEV is a registered trademark of Furukawa Electric Co Ltd in Japan Specifications are su...

Reviews: