<4–20 mA DC input>

Connection to Model SDC35TC0/SDC36TC0 

Connection to Model SDC35TC0/SDC36TC0 (Parallel operation)

Notes:

*

  Input impedance of the actuator is 100 

W

.

*

  For connecting multiple  ACTIVAL to one controller (e.g., Model SDC35/SDC36), provide a transformer (two in total) for each ACTIVAL

 

since 4 to 20 mA input is not isolated from other terminals.

*

  Terminals 2, 5, and 7 are connected inside the actuator.  To connect to a device (PLC, position indicator, etc.) with its terminals not 

isolated inside, externally isolate (between the ACTIVAL and the device).  Otherwise, a loop is formed for the common line and can 

damage the circuit of the ACTIVAL. (R series controllers including Model SDC35/SDC36 shown in Figs. 14 and 15 are isolated inside.)

*

  Isolation transformer is required for ACTIVAL.  Transformer without isolation may damage the ACTIVAL and other devices connected to 

ACTIVAL.

Model 

SDC35TC0/SDC36TC0

+ 13

- 14

1 T

1

2

T

2

4 +

5

-

6 +

7

-

Figure 15.    Connection example: Two Model VY519_J 

with Model SDC35TC0/SDC36TC0 (Parallel operation)

×

Model VY519_J

(4 to 20 mA DC input with 

4 to 20 mA DC output)

1 T

1

2

T

2

4 +

5

-

6 +

7

-

Power 

supply

Isolation

transformer

Power 

supply

Isolation

transformer

Position indicator

Isolator

+

-

+    +

-

-

Position indicator

Isolator

+

-

+    +

-

-

Isolation example:

If the position indicator is not isolated inside, provide 

an isolator. If isolated, an isolator is not required.

Model 

SDC35TC0/SDC36TC0

Model VY519_J

(4 to 20 mA DC input with 

4 to 20 mA

    DC output)

+ 13

- 14

1 T

1

2

T

2

4 +

5

-

6 +

7

-

Figure 14.    Connection example: Single Model VY519_J

with Model SDC35TC0/SDC36TC0

Power 

supply

Isolation

transformer

Position indicator

Isolator

+

-

+    +

-

-

Isolation example:

If the position indicator is not isolated inside, provide 

an isolator. If isolated, an isolator is not required.

Summary of Contents for ACTIVAL VY51 Series

Page 1: ...lable 4 20 mA DC input 2 10 V DC input Valve for chilled hot water control and for steam control applicable to high differential pressure large Cv value high rangeability and low leakage Durable actua...

Page 2: ...ency of use as basic parameters The recommended design life of this product is 10 years The recommended design life assumes that maintenance such as replacement of the limited life parts is carried ou...

Page 3: ...e UL50E Type 4 Enclosure 2 Only the actuator is certified with the UL cUL above CAUTION After installation make sure no fluid leaks from the valve pipe connections Improper piping may cause fluid leak...

Page 4: ...ristics Equal percentage Rangeability 100 1 Seat leakage Class IV 0 01 of rated Cv value Paint Gray Actuator to be combined Integrated with the valve Actuator specifications Item Specification Power s...

Page 5: ...t must be avoided Outdoor Use the outdoor cover etc to be ordered separately Direct sunlight salt air corrosive gas flammable gas and organic solvent must be avoided Installation orientation Installab...

Page 6: ...4 44 1 Figure 1 Dimensions and maintenance clearance Model VY51_FJ VY51_GJ Parts Identification Figure 2 Parts identification Note Leave a clearance of 4 100 mm if you do not open the top cover to se...

Page 7: ...ble for input output signal lines and power line Unshielded cable can cause error due to noise Identification of the selector switches Figure 3 Selector switches Open close selector switch for input s...

Page 8: ...w indicated on the valve body Do not install the product nearby a steam coil pressurized hot water coil or any high heat source High temperature radiation might cause malfunction of its actuator Insta...

Page 9: ...ve seat may get damaged causing fluid leakage due to the sealing material jammed inside the valve Before activating the ACTIVAL fully open in 100 position the valve and flush the pipes with the ACTIVA...

Page 10: ...he ACTIVAL before manually operating the ACTIVAL As shown in Fig 6 from the front of the ACTIVAL hold the joint using a tool such as a wrench and turn the joint slowly toward the set position Figure 6...

Page 11: ...tion to mount onto the valve 4 A thermal insulation sheet is inserted between the yoke and the valve When changing the mounting positions reinsert the sheet and then fit the yoke into the new mounting...

Page 12: ...ower supply and feedback signal and then correctly wire the product Incorrect wiring may result in PCB print circuit board burnout To prevent damage cover the terminals except when connecting disconne...

Page 13: ...sult in electric shock Terminals connection 2 10 V DC input Figure 10 Terminals connection of Model VY514_J 4 20 mA DC input Figure 11 Terminals connection of Model VY519_J 1 Unscrew the setscrews 2 R...

Page 14: ...isolated inside Isolation transformer is required for ACTIVAL Transformer without isolation may damage the ACTIVAL and other devices connected to ACTIVAL Model SDC35TD0 SDC36TD0 13 14 1 T1 2 T2 4 5 6...

Page 15: ...ired for ACTIVAL Transformer without isolation may damage the ACTIVAL and other devices connected to ACTIVAL Model SDC35TC0 SDC36TC0 13 14 1 T1 2 T2 4 5 6 7 Figure 15 Connection example Two Model VY51...

Page 16: ...Inspect the ACTIVAL according to Table 1 Manually open close the ACTIVAL at least once a month if it is left in inactive state for a long period Visually inspect the fluid leakage of the valve and th...

Page 17: ...alve vibrates or produces an abnormal noise Primary pressure condition Differential pressure condition Adjust the mounting position and change the installation location The auxiliary switch does not o...