14
AB-7489-U
Connection Examples (Connection to Azbil Corporation’s SDC series controller)
<2–10 V DC input>
Connection to Model SDC35TD0/SDC36TD0
Connection to Model SDC35TD0/SDC36TD0 (Parallel operation)
Notes:
*
Input impedance of the actuator is 100
W
.
*
For connecting multiple ACTIVAL to one controller (e.g., Model SDC35/SDC36), provide a transformer (two in total) for each ACTIVAL
since 2–10 V DC input is not isolated from other terminals.
*
Terminals 2, 5, and 7 are connected inside the actuator. To connect to a device (PLC, position indicator, etc.) with its terminals not
isolated inside, externally isolate (between the ACTIVAL and the device). Otherwise, a loop is formed for the common line and can
damage the circuit of the ACTIVAL. (R series controllers including Model SDC35/SDC36 shown in Figs. 12 and 13 are isolated inside.)
*
Isolation transformer is required for ACTIVAL. Transformer without isolation may damage the ACTIVAL and other devices connected to
ACTIVAL.
Model
SDC35TD0/SDC36TD0
+ 13
- 14
1 T
1
2
T
2
4 +
5
-
6 +
7
-
Figure 13. Connection example: Two Model VY514_J
with Model SDC35TD0/SDC36TD0 (Parallel operation)
2
×
Model VY514_J
(2–10 V DC input with
2–10 V DC output)
1 T
1
2
T
2
4 +
5
-
6 +
7
-
Power
supply
Isolation
transformer
Power
supply
Isolation
transformer
Position indicator
Isolator
+
-
+ +
-
-
Position indicator
Isolator
+
-
+ +
-
-
Isolation example:
If the position indicator is not isolated inside, provide
an isolator. If isolated, an isolator is not required.
Model
SDC35TD0/SDC36TD0
Model VY514_J
(2–10 V DC input with
2–10 V DC output)
+ 13
- 14
1 T
1
2
T
2
4 +
5
-
6 +
7
-
Figure 12. Connection example: Single Model VY514_J
with Model SDC35TD0/SDC36TD0
Power
supply
Isolation
transformer
Position indicator
Isolator
+
-
+ +
-
-
Isolation example:
If the position indicator is not isolated inside, provide
an isolator. If isolated, an isolator is not required.