2.11 Relè OK and regen resistance connections
REGEN RESiStaNcE connection
iNtERNal
resistance
EXtERNal
resistance
The cable must be as short as possible.
The resistances must be connected to the
zinced pannel utilising two screws.
If the cable length is greater than
20/30cm, it must be twisted and shielded.
The shield must be connected to ground
on both ends, utilising u-clamps to the
zinced panel of the electrical box.
attention: The internal braking
circuit is enabled only if a bridge is
present between pins 7 (-aT) and
8 (inT) on the m5 connector.
RElE' Ok connection
EXT
INT
-AT
U
V
W
PE
B+
B-
MAGNUM400
TM
M5
1
2
3
4
5
6
7
8
9
EXT
INT
-AT
U
V
MAGNUM400
TM
M5
5
6
7
8
9
F
4
PE
18
19
M2
MAGNUM400
TM
OPTIONAL
It is normally open when the drive is not supplied;
it is normally closed when the drive is supplied and
it has not active alarms.
30V
AC/DC
- 500mA max