Putting the AXIstorage Li SH system into operation
1.
Switch the DC disconnector on the left side of the AXIstorage Li SH to "on".
2.
Commission the storage system according to the operating manual of the connected
inverter.
4
Repair
The Energypack may only be opened and repaired by the manufacturer.
Defective Energypack may only be send back in consultation with the manufacturer or a company
commissioned by the manufacturer to the address provided by him.
5
Decommissioning, storage
5.1
Introduction
5.1.1
Safety regulations
Switch off the DC switch on the left side of the AXIstorage Li SH battery system.
Open the AXIstorage Li SH and unlock and disconnect both the patch cables and the power cables on
the Energypack Energypack.
Mask the power socket with insulating tape.
WARNING
Health hazard due to deep-discharging.
After more than six months of storage, the battery cells can be deeply discharged. This can lead to
chemical reactions within the cells, which result in the development of heat and gas, as well as
possible health hazards.
Recharge the module every six months.
All current legal fire protection requirements must be met. In case of doubt, contact your local fire
brigade and your insurance agency.
Store the Energypack in a dry place, protected from sunlight.
If the Energypack has been in water or any other liquid, it must not be put back into operation.