3.3.2 - Pre-flashing time
The flashing light is an important safety
component
. It starts when a command to set the
gate in motion is received by the electronic card.
The gate is set in motion around one second after a
command is received.
In certain use cases, it is better that the time
between receiving a motion command and the start
of the manoeuvre is longer. It is possible to increase
this time to 3 seconds.
To set the pre-flashing time, follow the
procedure below
• Press
PROG
for 3 seconds. L0 will flash once
and L1 will switch on.
• Press “
PROG
” for 3 seconds. L0 will flash twice.
• Press
PROG
for 3 seconds. L0 will flash 3 times.
• Press “
+
” once. L2 will turn on instead of L1.
• Press
OK
.
• If L1 is off, the time is 1 second. Press “
+
” to
increase it to 3 seconds, then
OK
to confirm. All
LEDs will turn on and off to confirm the operation.
• If L1 is on, the time is 3 seconds. Press “
–
” to
reduce it to 1 second, then
OK
to confirm. All
LEDs will turn on and off to confirm the operation.