2.9.2.5
Phase Rotation
Rectifier modules are not sensitive to phase rotation.
2.9.2.6
Phase Voltage
The Input Phase Voltage is detailed in Table 2–16.
Nominal voltage is a.c. r.m.s, 3 phase, 3-wire and earth/ground.
The equipment will operate with a variation of ±10% of the nominal supply voltage. For supply voltages below
the nominal, there will be a corresponding reduction in maximum output power. The equipment can operate
up to a maximum of +15% variation on the nominal supplies for a maximum of 30 cycles duration without the
equipment tripping though reduced performance may be observed.
Input AC Voltage
Output DC Link Voltage
Module
Nominal AC Input
Voltage (V r.m.s.)
Maximum
Output
(V d.c.)
Maximum Allowed
Regenerative Voltage
(V d.c.)
GDR391-4401
GDR633-4401
GDR721-4401
GDR872-4401
GDR1168-4401
380 - 480
780
800
GDR391-4601
GDR633-4601
GDR721-4601
GDR872-4601
GDR1168-4601
500 - 690
1122
1250
Table 2–21. – Input a.c. Voltage & Output d.c. Link Voltage Ratings
2.9.2.7
A.C. Voltage Frequency
Supply frequency
: 45 Hz to 63 Hz.
2.9.2.8
D.C. Link Voltage
The Output d.c. Link Voltage is detailed in Table 2–16.
Typical d.c. output:
1.35 x supply voltage (r.m.s).