![Avid Technology MV3000 DELTA Technical Manual Download Page 24](http://html1.mh-extra.com/html/avid-technology/mv3000-delta/mv3000-delta_technical-manual_3031206024.webp)
Specification
T1689 Technical Manual Rev 07
DRIVE PERFORMANCE WITH MV3000e CONTROLLER
MV3000 Air Cooled DELTA
Page 24
2.2.5.2
Transport & Storage
The levels in Table 2–7 are permitted only when the modules are packed for transport.
Vibration -
Storage and
transport
To IEC 61800-2 which specifies Class 2M1 of IEC 60721-3-2 when equipment is
packed for transport:
2 to 9 Hz
3.5mm amplitude
9 to 200 Hz
10m/s
2
acceleration
200 to 500 Hz
15m/s
2
acceleration
Drop -
Transport
To IEC 61800-2 which specifies Class 2M1 of IEC 60721-3-2 when equipment is
packed for transport:
mass < 100kg 0.25m; 100kg
≤
mass
0.10m
Table 2–7. – Transportation & Storage Vibration Levels
2.2.6
Inclination
Inclination levels for the DELTA power modules are defined below.
Condition
Severity
Static
List 15°, trim 5°
9 Hz to 200 Hz
±22.5°, pitch ±7.5° (may occur simultaneously)
Table 2–8. – Recommended Maximum Operational Vibration Levels
2.3
DRIVE PERFORMANCE WITH MV3000E CONTROLLER
Table 2–9 includes the drive performance data.
FREQUENCY
Resolution
0.01%
Control Accuracy
0.1%
SPEED
Resolution
0.01%
Accuracy (absolute)
0.01%
SPEED CONTROL
FREQUENCY CONTROL
(VVVF)
ENCODERLESS FLUX
VECTOR
FLUX VECTOR WITH
ENCODER
Range
50 : 1
50 : 1
>1000 : 1
Bandwidth
N/A
20 rad/s
100 rad/s
Accuracy
≅
1%
≅
0.5%
≅
0.02%
TORQUE CONTROL
Bandwidth
< 1 rad/s
> 500 rad/s
> 500 rad/s
Accuracy
≅
10%
≅
10%
≅
5%
Table 2–9. – Drive Performance Data