38
(9) F0- Outdoor Unit DC motor error (3-core terminal motor)
Explanation of
error
Cause:
Our frequency changing Outdoor Unit uses the 3-lead-wire DC
motor, or “Outdoor Unit driven DC motor” for short, after 2012. It has
no speed feedback circuit but 3 drive lead wires and its driving
principle is similar to that of the compressor. The main PCB will
indicate “Outdoor Unit DC motor error” when it detects imbalanced
current on the three lead wires of the driving motor.
Inspection path:
Is the DC motor stuck by foreign matters→Motor
terminal connectors→Outdoor Unit main PCB→Motor
Tools required
for inspection
Outdoor Unit main PCB in normal condition
Frequent
problematic part
Mechanical jam of Outdoor Unit motor, Outdoor Unit main PCB,
Outdoor Unit DC motor
Inspection
procedure and
key points
1. First exclude the possibility of mechanical jam of Outdoor Unit
motor blades.
。
2. Observe if the terminal of the motor is not connected firmly or the
order of lead wires is correct. If the Outdoor Unit motor of the newly
installed air conditioner rotates reversely, first observe if the color
order of the three lead wires is correct, or change the order of any two
of the three lead wires of the motor to see if the motor can rotate in the
forward direction.
3
.
The DC motor of this scheme is relatively simple and reliable, so the
problem is more likely to be caused by the drive part of the motor of
the Outdoor Unit main PCB. The maintenance personnel may as well
prepare matched Outdoor Unit main PCB before maintenance. If the
motor returns to normal after replacing the main PCB, then it’s the
main PCB problem; if it still indicates Outdoor Unit DC motor error,
then replace the Outdoor Unit DC motor.
Special attention
Unlike the 5-core Indoor Unit DC motor, there will be a process of
motor blade position locking before the 3-core DC motor with Outdoor
Unit drive starts to rotate. The motor blades will shake mechanically
for 3-5 seconds and then rotate slowly, which is normal phenomenon.
Summary of Contents for ASW-H09B5B4/FAR3DI-C3
Page 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Page 2: ...This manual is for professional maintenance personnel only ...
Page 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Page 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Page 18: ...15 18K 24K ...
Page 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Page 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Page 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Page 74: ...71 9 2 Outdoor Unit ...
Page 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Page 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Page 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Page 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Page 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Page 82: ...79 2 Remove top cover 3 Remove control box cover ...
Page 83: ...80 4 Remove panel grille 5 Remove front panel ...
Page 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Page 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Page 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Page 87: ...84 12 Remove reactor 13 Remove partition board ...
Page 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Page 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...