52
(21) P3 –Liquid Deficiency Protection
Explanation of
error
Cause: The liquid volume of the system is less than 30%, which leads
to non-refrigeration and liquid shortage protection.
Inspection path: whether the valves of the outdoor unit are opened
→
whether the evaporator, condenser, connectoin pipe are damanged or
cracked
→
whether the environmental temperature sensor and the coil
temperature sensor are damaged at the same time
Tools required
for inspection
Hex nut, multimeter, pressure gauge
Frequent
problematic part
Stop valve, evaporator, condenser and connection pipe
Inspection
procedure and
key points
1. Check the stop valve and turn it counterclockwise with hexagons to
see if the valve is not open and the opening is not enough;
2. Check whether the evaporator, condenser and connection pipe are
damaged or cracked, and focus on checking whether there is refrigerant
leakage in the welding part and connection pipe joint;
3. Measure the temperature sensor with the multimeter at ambient
temperature, and whether the coil temperature sensor has abnormal
resistance at the same time.
Summary of Contents for ASW-H09B5B4/FAR3DI-C3
Page 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Page 2: ...This manual is for professional maintenance personnel only ...
Page 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Page 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Page 18: ...15 18K 24K ...
Page 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Page 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Page 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Page 74: ...71 9 2 Outdoor Unit ...
Page 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Page 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Page 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Page 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Page 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Page 82: ...79 2 Remove top cover 3 Remove control box cover ...
Page 83: ...80 4 Remove panel grille 5 Remove front panel ...
Page 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Page 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Page 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Page 87: ...84 12 Remove reactor 13 Remove partition board ...
Page 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Page 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...