8-3 Troubleshooting for Normal Malfunction
26
The Foremost Inspecting Items
①
The input voltage must be 10% tolerance of the rated Voltage. If it is not
the case, the air-conditioner will probably not work normally.
②
Check the connecting cord between indoor unit and outdoor unit to see if it is
properly connected. The connecting must be done according to the wiring diagram,
please also notice that even different models may have the connecting cord of the
same specification. Please check if the marks at the connecting terminal and the marks
on the cord can match, otherwise, the air-conditioner will not work normally.
③
If the following phenomena are found, the problem is not from the air-conditioner
itself.
NO.
Problems
Causes
1
The motor is heard operating but
the air-conditioner does not work
when the indoor unit is powered on
Since the air-conditioner is powered on,
it will come to working condition as
long as you press the ON/OFF button of
the remote control and the Signal is well
received.
2
The compressor stops running but
the indoor motor keeps working
when it is at cooling mode with the
indoor temperature higher than set
temperature.
If you turn off the air-conditioner and
restart it immediately, it will return to
normal in 3 minutes, after that, the
air-conditioner will automatically adjust
the indoor motor speed to what you set.
3
The compressor works
discontinuously at dehumidifying
mode.
The air-conditioner will automatically
control the working of the compressor
according to the inside temperature.
4
The air-conditioner does not work
while the LED display is on.
The TIMER is set with the A/C; it will
be in hold on condition. If the TIMER
setting is cancelled, the air-conditioner
will return to normal working condition.
5
The compressor works
discontinuously at cooling and
dehumidifying mode, and the
indoor motor slows down.
The compressor stops Indoor Unit or the
motor slows down to prevent the indoor
heat exchanger from being frozen.
Summary of Contents for ASW-H09B5B4/FAR3DI-C3
Page 1: ...AUX Imp Exp Company Limited F Freedom Inverter Split Type Air Conditioner ...
Page 2: ...This manual is for professional maintenance personnel only ...
Page 7: ...4 2 2 Outdoor Unit 1 3P 1 8P 新 2P 2 3P ...
Page 17: ...14 5 Electrical Part 5 1 Wiring Diagram Indoor Unit 09K 12K 18K 24K Outdoor Unit 09K 12K ...
Page 18: ...15 18K 24K ...
Page 19: ...16 Part II Installation and Maintenance 6 Main Tools for Installation and Maintenance ...
Page 71: ...68 Remote Control Can Not Work Trouble shooting procedure ...
Page 72: ...69 9 Exploded Views and Parts List 9 1 Indoor Unit ...
Page 74: ...71 9 2 Outdoor Unit ...
Page 77: ...74 3 Remove air louver 4 Remove air filter 5 Remove Medium frame wiring cover ...
Page 78: ...75 6 Remove medium frame 7 Remove Control the lid 8 Remove Electric box ...
Page 79: ...76 9 Remove press plate 10 Remove component 11 Remove pipe clamp ...
Page 80: ...77 12 Remove evaporator 13 Remove the blade 14 Remove Motor press plate ...
Page 81: ...78 15 Remove Motor 10 2 Outdoor Unit Part Procedure Diagram 1 Outdoor unit ...
Page 82: ...79 2 Remove top cover 3 Remove control box cover ...
Page 83: ...80 4 Remove panel grille 5 Remove front panel ...
Page 84: ...81 6 Remove E part cover 7 Remove right side panel ...
Page 85: ...82 8 Remove axial flow blade 9 Remove outer motor ...
Page 86: ...83 10 Remove electric box assy 11 Remove motor support ...
Page 87: ...84 12 Remove reactor 13 Remove partition board ...
Page 88: ...85 14 Remove left side support plate 15 Remove pipeline assembly ...
Page 89: ...86 16 Remove stop valve assembly 17 Remove valve plate ...