Testing indicator lights and internal buzzer
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 23
s
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarms
Contr.
Al -outp.
Fault/Disabled/Test
Battery
Power
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4
Fault outp.
.
Operator
Imm. alarm
Information
Alarm
System
Zone
Operator
1:
2:
3:
4:
Access code: xxx
Silence int. buzzer
Silence/res. alarms
Reset
Autronica Fire & Security
System
0
C
9
8
7
6
5
4
3
2
1
BX-10
R
R
Alarm call activated
Activating from an auxiliary switch
An auxiliary switch for activating/deactivating the alarm delay function can
be connected to
terminals 60 and 64
in the control panel. The alarm
delay is activated when the switch is closed. This is a standard
connection on the BX-10M1 panel.
Step
Necessary Action
Visual Warning Status
Audio Warning Status
1
Disable immediate
warning by closing the
auxiliary switch.
2
Restore immediate
warning function by
resetting auxiliary
switch.
Note:
The alarm delay on the alarm outputs and general common alarm output
(pre-programmed to 2 minutes) will be activated.
New delay period is activated by cancelling and re-activating the auxiliary
disabling switch.
No indication of delayed
alarm outputs.
Summary of Contents for BX-10M1