Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 14
s
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarms
Contr.
Al -outp.
Fault/Disabled/Test
Battery
Power
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4
Fault outp.
.
Operator
Imm. alarm
Information
Alarm
System
Zone
Operator
1:
2:
3:
4:
Access code: xxx
Silence int. buzzer
Silence/res. alarms
Reset
Autronica Fire & Security
System
0
C
9
8
7
6
5
4
3
2
1
BX-10
R
R
Alarm call activated
5. Fire alarm with 2 minutes delayed
warning
The BX-10M1has according to SOLAS requirements 2 minutes delay of sounder outputs.
Step
Necessary Action
Visual Warning Status
Audio Warning Status
1
Follow local fire instructions
step by step.
The red FIRE indicator
flashes.
One of the red zone indicators
at the bottom-left will flash to
indicate in which detection
zone the fire is detected (zone
1, 2, 3 or 4).
The integrated audio warning
device with continous signal
is activated.
Note:
Two-minute alarm delay starts (two minute alarm delay applies
to maritime regulation).
Immediate alarms are disabled during the delay period.
If an alarm is given from two or more detectors or detection
zones simultaneously, the alarm outputs will be activated
immediately, i.e. the alarm delay will be interrupted.
2
Silence internal buzzer by
pressing
The red FIRE indicator and
zone indicator will continue to
flash.
The internal buzzer is
switched off.
3
Accept the alarm by
pressing
The flashing red indicators
change to a steady light. The
running delay time is
deactivated.
Alarm outputs are blocked for
automatic activation.
Note:
If necessary, the sounders can be reactivated by once again
operating
4
Investigate the fire site of fire
and all detectors on the
alarming loop to check if there
are more than one area in fire.
(Continued on next page…..)
One or more detectors/manual call-points send an alarm signal from a detection zone in a situation where
alarm delay
is activated (immediate warning disabled, see Chap. 8).
NOTE: If an alarm is activated from
two or more
detection zones simultaneously, the alarm
outputs and alarm transference will be activated immediately, i.e. the alarm delay will be
cancelled. The same activation will appear if a manual call point without an extra resistor
is operated in a zone. Refer to chapter 1.1.
The red FIRE indicator flashes.
Red flashing zone lights
indicate which detector
zone(s) are involved.
Visual characteristics:
0.5 sec. ON – 0.5 sec. OFF
Continuous audio signal.
All alarms linked to the
panel are delayed 2
minutes.
Continuous alarm
signal for maritime
version.