Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 15
4
The next step in the procedure will depend on whether or not there really is a fire.
Step should be followed if there
isn’t
a fire, step if there
is
a fire.
4a
If there is
not
a fire;
go into operator mode: key in
operator code +
The yellow
operator level
indicator will
come on.
5a
Reset the system by operating
The red FIRE
indicator and
zone indicator
will go out.
4b
If there really
is
a real fire,
implement the necessary
measures. Activate the fire
alarm and alert the fire
department by activating the
nearest manual call-point.
The red FIRE indicator and
zone indicator will continue to
flash.
All sounders will be switched
on.
General alarm output will be
activated.
Note:
When the fire is extinguished and all necessary repair work is
complete (the smoke is exhausted, new glass replaced in the
manual call-points, etc.), the system may be returned to normal
operating mode again.
5b
If the Operator Mode is
switched off, re-enter the
Operator Mode again.
Go into operator mode: key in
operator code +
The yellow operator level
indicator will come on.
Note:
If the system goes out of operator mode after 5minutes, you
must re-enter the operator code +
6b
Silence alarm by pressing
The red FIRE indicator and
the zone indicator(s) will
come on with a steady light.
All sounders will be switched
off.
General alarm output remains
activated.
Note:
If necessary, the sounders may be re-activated by pressing
again.
7b
Reset the system by pressing
The red FIRE indicator and
zone indicator(s) will go out.
Note:
If a detector zone remains in alarm status after resetting the
system, the alarm will be activated again. In such an instance
the above steps must be repeated.
4a
R
4b
R