Disabling/restoring
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 19
s
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarms
Contr.
Al -outp.
Fault/Disabled/Test
Battery
Power
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4
Fault outp.
.
Operator
Imm. alarm
Information
Alarm
System
Zone
Operator
1:
2:
3:
4:
Access code: xxx
Silence int. buzzer
Silence/res. alarms
Reset
Autronica Fire & Security
System
0
C
9
8
7
6
5
4
3
2
1
BX-10
R
R
Alarm call activated
7.2 Disabling/restoring from the front panel
Step
Necessary Action
Visual Warning Status
Audio Warning Status
1
Key operator code (110) +
The yellow OPERATOR
LEVEL indicator will come
on.
Note:
In operator mode, the keys numbered 1-8 represent the
following disabling operations:
Key 1: disabling of zone 1
Key 2: disabling of zone 2
Key 3: disabling of zone 3
Key 4: disabling of zone 4
Key 5: disabling of alarm outputs (AK1, AK2)
Key 6: disabling of control outputs
(zone outputs 1-4, AUX 1 and 2, fire doors)
Key 7: disabling of alarm outputs (BMA) FARE
Key 8: disabling of fault output (BMF) FWRE
Key 9: disabling of immediate warning (delayed alarm)
2
Press the
respective key (1-8) +
The yellow common
DISABLING indicator will
come on.
One (or more) of the yellow
indicators in the
FAULT/DISABLING/TEST
field will come on indicating
the type of disabling.
Note:
Restoring functions:
The yellow common DISABLING indicator and indicator for
the respective function will go out as soon as the function is
cancelled, i.e. when the function is
manually restored
.
Functions are
restored
manually by implementing the same
procedure for the function concerned. E.g. zone 1 is restored by
keying 1 + .
In this example the yellow LED indicator for ZONE 1 will go
out.
The common yellow
DISABLING indicator
will come on.
One (or more) of the
yellow indicators in the
FAULT/DISABLING/T
EST field will come on
indicating the type of
disabling.
The operator can
disable
one or more zones (detector loops 1-4), alarm outputs, control outputs,
and/or general alarm and error outputs.
Restoration
is implemented manually following the same procedure.
The yellow
OPERATOR LEVEL
indicator will come on.
Note!
The panel also provides the disabling function 10 and 11, but they are not used for any
functions. If the code for 10 or 11 is operated by a mistake, the common disable LED
will light up. If this occurs, the operator has to make a disable /enable for both code 10
and 11 to see if the common disable LED is switched off.