Instructions, AutroFlame X33AFPL, 116-P-X33AFPL/IGB, rev . A, 2016-11-04
P/N 95-8750, v2 .4, rev . 1/16
Autronica Fire and Security AS
Page D-1
APPENDIX D – IECEX APPROVAL
IECEx CERTIFICATE OF CONFORMITY
DEMKO
IECEx ULD 06 .0017X
Ex db eb IIC T6...T5
Ex db IIC T6...T4
Ex tb IIIC T130°C
T6 (Tamb = –55°C to +60°C)
T6 (Tamb = –50°C to +60°C) or T5 (Tamb = –55°C to +75°C)
T5 (Tamb = –50°C to +75°C)
T4 (Tamb = –55°C to +125°C)
IP66
IP66/IP67
Compliance with:
IEC 60079-0: 2011, Ed. 6
IEC 60079-1: 2014, Ed. 7
IEC 60079-7: 2015, Ed. 5
IEC 60079-31: 2013, Ed. 2
IEC 60529: 2013, Ed. 2.2
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from
14-24 AWG or 2 .5-0 .2 mm
2
.
The Multispectrum infrared (IR) flame detector type X33AF PL shall be installed according to the instructions given by
the manufacturer .
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the terminal
compartment in type of explosion protection flameproof enclosure "d" or in type of explosion protection increased safety
"e" for use with the terminal compartment in type of explosion protection increased safety "e" .
They shall be IP66 rated, suitable for the conditions of use and correctly installed .
Unused entries shall be closed with suitable certified blanking elements .
The metal housing for the Multispectrum infrared (IR) flame detector type X33AF PL must be electrically connected to
earth ground .
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature .
Special conditions for safe use:
The front window assembly contains a special cemented joint construction . In accordance with EN60079-1 clause 5 .1 .c,
all inspections, repair and/or adjustments to this front window assembly shall be done by the manufacturer only .
The EOL resistor can only be used within the flameproof terminal compartment . EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power dissipation not to exceed 2 .5 watts .
The Multispectrum infrared (IR) flame detector type X33AF PL is to be installed in places where there is a low risk of
mechanical damage .
• See the "Maintenance" section of this manual for guidance on minimizing the risk from electrostatic discharge .
• Flameproof joints are not intended to be repaired . See the "Device Repair and Return" section of this manual for
more information on conducting repairs .
The following accessories are IECEx approved for use with the X33AF PL Flame Detector:
Part Number
Description
116-007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
116-007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
116-011385-001
Q9033 Collar Attachment