APPENDIX A – FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:
•
Explosion-proof for Class I, Div . 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615 .
•
Dust-ignition proof for Class II/III, Div . 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615 .
•
Nonincendive for Class I, Div . 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611 .
•
Nonincendive for Class II, Div . 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611 .
•
Enclosure rating NEMA/Type 4X per NEMA 250 .
•
Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C) .
•
Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000) .
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
CL I, ZONE 1, AEx db eb IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T130°C
Tamb –40°C to +75°C
IP66
CL I, ZONE 1, AEx db IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
IP66/IP67
The following accessories are FM approved for use with the X33AF PL Flame Detector:
Part Number
Description
116-102740-002
Magnet
116-007739-001
Magnet and Extension Pole
116-010857-001
Q1130A1001 Flange Mount Assembly
116-007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
116-007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
116-011385-001
Q9033 Collar Attachment
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated Automatic
Optical Integrity (
oi
) test for each sensor . Upon removal of the contamination, the detector fault was cleared and the
detector was verified to detect a fire .
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic
oi
performs the same calibrated test as the Automatic
oi
, and additionally actuates the alarm
relay to verify output operation . If there is a 50% loss of its detection range, an alarm signal is not generated .
The Optical Integrity test procedure, as described in the "Magnetic
oi
/ Manual
oi
" section of this instruction manual, is
the approved external optical test method for this detector to verify end-to-end detector function . This test replaces the
function and need of a traditional external test lamp .