background image

Operating instructions

Electronic pressure sensor

autosen 

AP006 - AP010

80237495 00 04 /2016

Made in Germany

UK

Summary of Contents for AP006

Page 1: ...Operating instructions Electronic pressure sensor autosen AP006 AP010 80237495 00 04 2016 Made in Germany UK Made in Germany ...

Page 2: ...ion of the menu level 1 14 8 2 2 Explanation of the menu level 2 14 9 Parameter setting 15 9 1 Parameter setting in general 15 9 2 Configure display optional 17 9 3 Set output signals 18 9 3 1 Set output functions 18 9 3 2 Define switching limits for the hysteresis function 18 9 3 3 Define switching limits for the window function 18 9 3 4 Scaling of the analogue value 19 9 4 User settings optional...

Page 3: ... 9 4 8 Set colour change of the display 20 9 4 9 Graphical depiction of the colour change of the display 21 10 Operation 23 10 1 Read set parameters 23 10 2 Self diagnosis error indications 24 11 Technical data and scale drawing 25 11 1 Setting ranges 25 11 2 Further technical data 26 12 Factory setting 27 ...

Page 4: ...ith the media to be measured in all applications Correct condition of the device for the operating time can only be guaranteed if the device is only used for media to which the wetted materials are sufficiently resistant 3 1 Applications If the devices are used in gas applications with pressures 25 bar the notes in chapter 3 1 for devices with the marking must be absolutely observed The responsibi...

Page 5: ... bar for gas applications 25 bar MPa measured value in bar 10 kPa measured value in bar x 100 Avoid static and dynamic overpressure exceeding the specified overload pressure by taking appropriate measures The indicated bursting pressure must not be exceeded Even if the bursting pressure is exceeded only for a short time the unit may be destroyed ATTENTION Risk of injury The units are vacuum resist...

Page 6: ...munication So the following options are possible Remote display reading and display of the current system pressure Remote parameter setting reading and changing the current parameter setting IO Link parameter setting 4 4 4 1 Communication parameter setting evaluation OUT1 pin 4 Switching signal for system pressure limit value Communication via IO Link OUT2 pin 2 Switching signal for system pressur...

Page 7: ...int SPx is set then the reset point rPx The hysteresis defined remains even if SPx is changed again Window function normally open ou1 ou2 Fno fig 2 Window function normally closed ou1 ou2 Fnc fig 2 The width of the window can be set by means of the difference between FHx and FLx FHx upper value FLx lower value FH FL 1 2 P system pressure HY hysteresis FE window When set to the window function the ...

Page 8: ...ich measured value the output signal is 20 mA or 10 V Minimum distance between ASP2 and AEP2 20 of the measuring span Voltage output 0 10 V Factory setting Measuring range scaled P System pressure VMR Final value of the measuring range ASP Analogue start point ASP2 AEP Analogue end point AEP2 In the measuring range of the respective unit the output signal is between 0 and 10 V It is also indicated...

Page 9: ... below ASP2 4 3 8 mA Fault indication according to Namur 21 5 mA 4 4 IO Link General information This unit has an IO Link communication interface which requires an IO Link capable module IO Link master for operation The IO Link interface enables direct access to the process and diagnostic data and provides the possibility to set the parameters of the unit during operation In addition communication...

Page 10: ...on about the required IO Link hardware and software at www autosen com 5 Installation Before installing and removing the unit make sure that no pressure is applied to the system Insert the unit in a G process connection Tighten firmly Recommended tightening torque Pressure range in bar Tightening torque in Nm 1 400 25 35 600 30 50 Depends on lubrication seal and pressure load The sensor housing ca...

Page 11: ...ws Core colours 4 3 2 1 BN WH BK BU 4 1 3 2 OUT2 L L OUT1 BK black BN brown BU blue WH white OUT1 switching output or IO Link OUT2 switching outputs or analogue output Colours to DIN EN 60947 5 2 Example circuit 2 x positive switching 2 x negative switching L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 1 x positive switching 1 x analogue 1 x negative switching 1 x ana...

Page 12: ...System pressure in the indicated unit of measurement pin connection is device specific 9 Enter button Selection of the parameters and acknowledgement of the parameter values 10 to 11 Arrow keys up and down Setting of the parameter values scrolling by holding pressed incremental by pressing once 12 Alphanumeric display 4 digits Display of the current system pressure Indication of the parameters and...

Page 13: ...13 UK 8 Menu 8 1 Menu structure main menu 2 RUN 1 Menu items highlighted in grey e g FH1 are only active when assigned parameters have been selected ...

Page 14: ...ion H or window function F either normally open no or normally closed nc ou2 Output function for OUT2 Switching signal for the pressure limit values hysteresis function H or window function F either normally open no or normally closed nc Analogue signal for the current system pressure 4 20 mA I or 0 10 V U dS1 dS2 Switching delay for OUT1 OUT2 dr1 dr2 Switch off delay for OUT1 OUT2 uni Standard un...

Page 15: ... Press to edit the selected parameter Press or for min 1 s After 1 s setting value is changed incrementally by pressing the button once or continuously by keeping the button pressed Numerical values are incremented continuously with or decremented with 3 Acknowledge parameter value Briefly press The parameter is displayed again The new setting value is saved Set other parameters Press or until the...

Page 16: ...ith a parameter setting software Change from menu level 1 to menu level 2 Press to get to the menu Press until EF is displayed Press The first parameter of the submenu is displayed here rES Locking unlocking The unit can be locked electronically to prevent unintentional settings Make sure that the unit is in the normal operating mode Press simultaneously for 10 s Loc is displayed 10 s During opera...

Page 17: ...nchanged values Exit a parameter without adopting the settings To exit a parameter without adopting the settings Press simultaneously Return to the menu level Leaving the menu level To leave the menu level Press simultaneously Menu level 2 changes to level 1 or level 1 changes to display 9 2 Configure display optional Select Uni and set the unit of measurement bAr mbAr MPA kPA PSI inHG iH2O mmWS T...

Page 18: ...s 9 3 1 Set output functions Select ou1 and set the switching function Hno hysteresis function NO Hnc hysteresis function NC Fno window function NO Fnc window function NC Select OU2 and set the analogue function Hno hysteresis function NO Hnc hysteresis function NC Fno window function NO Fnc window function NC I current signal 4 20 mA U voltage signal 0 10 V 9 3 2 Define switching limits for the h...

Page 19: ...time is not active For this unit the parameters dSx and drx for the set and reset points are designed strictly to the VDMA guideline 9 4 2 Set output logic for the switching outputs Select P n and set PnP or nPn 9 4 3 Set damping for the switching signal Select dAP and set the damping constant in seconds value T 63 setting range 0 000 4 000 s Damping affects dAP the switch point process data flow ...

Page 20: ... display colour green when OUT1 switches r2ou display colour red when OUT2 switches ou2 Hxx Fxx G2ou display colour green when OUT2 switches ou2 Hxx Fxx r 12 display colour red when the measured value is between the limit values of OUT1 and OUT2 ou2 Hxx Fxx G 12 display colour green when the measured value is between the limit values of OUT1 and OUT2 ou2 Hxx Fxx r cF display colour red when the me...

Page 21: ...steresis function 1 OUT1 OUT2 2 1 2 OUT1 OUT2 Measured value switch point OUT1 OUT2 Display red Measured value switch point OUT1 OUT2 Display green Display colour change for the parameters r1ou r2ou mode window function Display colour change for the parameters G1ou G2ou mode window function 1 2 FL1 FL2 FH1 FH2 1 2 FL1 FL2 FH1 FH2 Measured value between FL1 FL2 and FH1 FH2 Display red Measured valu...

Page 22: ...n Display colour change for the parameters r 12 mode window function Display colour change for the parameters G 12 mode window function 1 FL1 2 FH1 FL2 FH2 1 FL1 2 FH1 FL2 FH2 Measured value outside FL1 FH1 and FL2 FH2 Display red Measured value outside FL1 FH1 and FL2 FH2 Display green Colour change display green Colour change display red 1 Initial value of the measuring range 2 Final value of th...

Page 23: ...ange cFL Lower limit value independent of the output function cFH Upper limit value independent of the output function 10 Operation After power on the unit is in the Run mode normal operating mode It carries out its measurement and evaluation functions and provides output signals according to the set parameters Operation indication 7 Operating and display elements 10 1 Read set parameters Press Pr...

Page 24: ...ive current remove the fault SC1 flashes flashes F Excessive current at switching output OUT1 Check switching output OUT1 for short circuit or excessive current remove the fault SC2 flashes flashes F Excessive current at switching output OUT2 Check switching output OUT2 for short circuit or excessive current remove the fault Loc W Parametrierung über Tasten gesperrt Unlock buttons 9 1 Parameter se...

Page 25: ...act the manufacturer F fault W warning The output remains deactivated as long as the excessive current short circuit continues 11 Technical data and scale drawing 11 1 Setting ranges SP rP ASP2 AEP2 cFH cFL ΔP min max min max min max min max min max min max AP010 bar 2 5 400 1 398 5 0 320 80 400 1 5 400 0 398 5 0 5 psi 40 5800 10 5780 0 4640 1160 5800 20 5800 0 5780 10 MPa 0 25 40 0 1 39 85 0 32 8...

Page 26: ...25 0 95 24 9 1 20 4 25 0 9 25 1 24 9 0 05 psi 12 362 5 13 5 361 14 5 290 58 362 5 13 362 5 14 5 361 0 5 MPa 0 085 2 5 0 095 2 49 0 1 2 0 4 2 5 0 09 2 5 0 1 2 49 0 005 AP006 bar 0 94 10 0 98 9 96 1 8 1 10 0 96 10 1 9 96 0 02 psi 13 6 145 14 2 144 4 14 6 116 14 6 145 13 8 145 14 6 144 4 0 2 MPa 0 094 1 0 098 0 996 0 1 0 8 0 1 1 0 096 1 0 1 0 996 0 002 ΔP Schrittweite 11 2 Further technical data Furt...

Page 27: ...EP2 100 MEW coF 0 dSx 0 0 drx 0 0 P n PnP dAP 0 06 dAA 0 1 diS d2 uni bAr mbAr coLr rEd cFH VMR cFL MAW Final value of the measuring range MEW Initial value of the measuring range MAW The indicated percentage of the final value of the measuring range VMR of the respective sensor is set More information at www autosen com ...