31
8.2 Parameters
SPx/rPx
Switching thresholds of the set points (SPx) and reset points (rPx) for
outputs OUT1 and OUT2�
The values for SPx/rPx are set in percent of the max� process value� The
process value is defined as follows:
Process value in air = 0 %
Process value in tap water = 100 %
Minimum hysteresis: 2 %
Type of medium:
Reference values:
Aqueous / water-based media:
SPx = 70 %, rPx = 62 %
(factory setting)
Media with low water content:
SPx = 35 %, rPx = 29 %
Oils, fats, powdery media:
SPx = 8 %, rPx = 5 %
oux
Output function for OUTx:
-[Hno] = hysteresis function/NO
-[Hnc] = hysteresis function/NC
-[Fno] = window function/NO
-[Fnc] = window function/NC
FOUx
Response of the outputs OUTx in case of a fault�
-[OFF] = switching output switches OFF in case of a fault�
-[On] = output switches ON in case of a fault�
dSx
Switching delay for OUTx�
Setting range 0…10 s� Step increment 0�1 s�
drx
Switch-off delay for OUTx�
Setting range 0…10 s� Step increment 0�1 s�
P-n
Switching logic for the outputs (PnP or nPn)
8.3 System commands
tSP1
Teach to medium 1
• Full adjustment to the medium 1 to be detected, automatically sets the
switching thresholds SP1/rP1 for OUT1�
tSP2
Teach to medium 2
• Full adjustment to the medium 2 to be detected, automatically sets the
switching thresholds SP2/rP2 for OUT2�
rES
Restoring the factory settings
UK