When installed in restricted spaces (e�g� pipes, tank corners, structures) or in
agitators and other moving objects:
►
To avoid malfunction and damage on sensor
and plant, adhere to a distance of the sensor
tip of min� 15 mm to neighbouring objects (e�g�
pipe/tank walls, structures, other LM sensors)
(Fig�
5-1)�
15 mm
15 mm
5.2 Installation procedure
5.2.1 Front installation for AF005
►
Slide the supplied flat seal over the thread onto the sensor and/or verify its
correct position�
►
Slightly grease the thread of the sensor using a lubricating paste which is suita-
ble and approved for the application�
►
Screw the sensor into the respective process connection and tighten it�
Max� tightening torque:
20���25 Nm
►
After installation check the tank/pipe for ingress resistance�