25
Lateral installation:
Since the probe tip is installed further into the tank, very adhesive and viscous
residues can be suppressed�
5 Mounting
Before installing and removing the unit: Make sure that no pressure is
applied to the system and there is no medium in the pipe or the tank�
Also always note the potential dangers related to extreme machine and
medium temperatures�
5.1 Installation location / environment
• Installation preferably in closed, metal tanks/pipes�
• The sensor must be in electrical contact with the metal process connection�
In applications subjected to pressure:
►
Only use process connections suitable and robust enough for the
process / the application�
When installed in plastic tanks, there may be deterioration caused by
electromagnetic interference�
►
Check the function by an application test�
In case of interference:
►
Take suitable measures (grounding, shielding ���) etc�
UK