X-30

ARD-A Series

 

Functions

Model

ARD-AI04

(input model)

ARD-AO04

(output model)

Basic 

Com. speed auto-recognition
Network power voltage monitoring
Unit power on total time monitoring
Unit comment
Last maintenance data stored

Analog

Scaling
I/O comment
Adjustment gradient
Adjustment offset
Input conversion points setting

-

Input digital filter

-

Peak/Bottom hold

-

Disconnected cable detection

-

Input comparison

-

Hysteresis

-

Output setting for error

-

 Communication speed auto-recognition

It recognizes communication speed when connecting 

master. Communication speed is able to change only from 

master unit.

After changing communication speed, re-supply the 

network power to apply the changed communication 

speed. 

 Network power voltage monitoring

● If 

network power voltage is lower than the set value, the 

network power voltage drop flag bit of Status bit is ON. 

It can be read by Configurator or Explicit message.

● 

Set monitoring voltage by Explicit message at Network   

Power voltage (Set Value) of Application Object.    

● 

Setting range: 0 to 255

(factory default: 12V, Allowable range: ±1V)

 

Min. supplied power is 12V for ARD unit.

If network voltage is lower than 12V, the contents of 

Explicit message reading is not guaranteed.

 Unit power on total time monitoring

● 

When total time for supplying power to the unit 

becomes the SV, Threshold Run Hours Flag bit of 

Status Bit turns ON. It can be read by Configurator or 

Explicit message.

● 

Set the time by Explicit message at Threshold Run 

Hour of Application Object.

● 

Setting range: 0 to 429,496,729 hours 

(factory default: 876,000 hours), 

  Measured unit: 0.1 hours (6 minutes)

 Unit comment

● You can set the comments for the unit (product 

description) on network. It can be read by Configurator 

or Explicit message.  

● Set comment by Explicit message at Unit Comment of 

Application Object.

● Setting range: max. 32 characters

 Last maintenance date

● 

It saves the last date of maintenance. It can be read/ 

written by Configurator or Explicit message.

● 

Set maintenance date by Explicit message at I/O Last 

Maintenance Data Setting of Analog Input Point Object. 

E.g.) Data: 0x07DB020E→07DB (2011), 02 (Februray), 

0E (14th)

 Input conversion points setting

● Conversion cycle is changed by the number of points 

(point, channel). 

 (conversion cycle: 1ms/point, when using 4 points, 

it is 4ms). It can be read/written by Configurator 

or Explicit message. After changing the number of 

conversion points, re-supply the network power. 

● Set the number of conversion points by Explicit 

message at Number of AD Conversion Points Setting 

of Analog Input Point Object. 

● Setting range: 

1 to 4-point

 (factory default: 4-point),   

  conversion cycle: 1ms/1-point

 

Display scale

● Set high/low-limit scale value of analog input or output. 

   It can be read by Configurator or Explicit message.

Default

Scaling  

Function Choice

: Scaling Flag bit ON

Scaling Type

: Default Scaling

(factory default)

It is set as 1,000 per 1V (mA). 

In case of 1-5V, 4-20mA, it is 

applied from over min. allowable 

range 0.8V (800), 3.2 (3,200). 

The below input value is break 

detection. It outputs as min. 

allowable range. 

None

Scaling

Function Choice

: Scaling Flag bit 

OFF

Scaling Type

: Default Scaling

It is set as default value 0 to 

16000 (-8000 to 8000).

(0-5V, 1-5V, 0-10V, 4-20mA, 

0-20mA: 0 to 16000, -5-5V, -10-

10V: -8,000 to 8,000 )

User

Scaling

Function Choice

: Scaling Flag bit ON

Scaling Type

: User Scaling 

Set high/low-limit value to apply 

at ‘Scaling Point 0%’ and ‘Scaling 

Point 100%’.

Setting range: -28,000 to 28,000

Summary of Contents for ARD-A Series

Page 1: ...esis reading model name and number of units I O and status flag monitoring Built in surge ESD protection Reverse polarity protection circuit Mounting DIN rail method and bolt mounting method I O points I O type Digital Analog Network Item AR D A 04 4 point type A Analog type D 1 Digital type D DeviceNet type AR Autonics Remote I O I Input type O Output type 1 For digital type refer to ARD D Series...

Page 2: ...istance max 600Ω Max allowablerange 5 F S of rated input range 5 F S of rated output range Resolution 14bit 1 16 000 Accuracy At room temperature 25 5 range 0 3 F S Out of room temperature range 0 6 F S Insulation resistance Over 200MΩ at 500VDC megger Noise immunity 240V the square wave noise pulse width 1 by the noise simulator Dielectric strength 500VAC 50 60Hz for 1 min between external termin...

Page 3: ...DIP switches SW1 to SW6 By turning OFF SW8 I O range is set by communication When setting I O range by DIP switches CH0 and CH1 CH2 and CH3 cannot be set individually When setting it by communication each channel is set individually 6 I O Terminal block It is terminal block for connecting external device I O No Color For Organization 5 Red 24VDC V CAN_H SHIELD CAN_L V 4 White CAN_H 3 None SHIELD 2...

Page 4: ...NS Green 4 MS Red Watchdog timer error The status that DIP switch or another switch setting is invalid Change the switch with valid value and re supply the power NS 5 MS Red Switch setting error The status that DIP switch or another switch setting is invalid Change the switch setting to valid value and re supply the power NS 6 MS Red Changed address during normal operation The status that address ...

Page 5: ...ower circuit Output circuit Power circuit V OUT COM I OUT COM Load Max 1KΩ Load Max 600Ω Analog GND Terminating Resistance 120Ω 1 of metallic film 1 4W Do not install terminating resistance on ARD unit or it may cause network problem impedance can be too high or low or malfunction Connect terminating resistance on the both ends of the trunk line Communication Distance Baud Rate Max network length ...

Page 6: ...e to the DeviceNet connector and tighten the fixed bolt of the connector by a driver tightening torque 0 5N m Connect the DeviceNet connector to ARD unit and supply the power to Network PIN No Signal 5 V 4 CAN_H 3 SHIELD 2 CAN_L 1 V PIN No Signal 5 V 4 CAN_H 3 SHIELD 2 CAN_L 1 V Master unit Black ARD unit 5 Red V 4 White CAN_H 3 None SHIELD 2 Blue CAN_L 1 Black V Red White None Blue Setting of mas...

Page 7: ...t You can set the comments for the unit product description on network It can be read by Configurator or Explicit message Set comment by Explicit message at Unit Comment of Application Object Setting range max 32 characters Last maintenance date It saves the last date of maintenance It can be read written by Configurator or Explicit message Set maintenance date by Explicit message at I O Last Main...

Page 8: ...mpling cycle It is able to read write by Configurator or Explicit message It is applied when Moving Average is set as ON at Function Choice of Analog Input Point Set the number of digital filters at Moving Average Filter of Number Setting range 0 to 8 factory default 3 Moving Average No_8 When operating analog input cable voltage current input is disconnected Broken Wire Flag Bit turns ON at Analo...

Page 9: ...a by Configurator or Explicit message By property setting assignment is available as Analog Input Value Peak Value Bottom Value Assembly Instance ID 103 Default 0 Setting range 0 to 2 Analog Input Value 0 Peak Value 1 Bottom Value 2 Data type Word Data size 4Word 0 15 Assigned value to Analog Data 1 of Input point 0 Assigned value to Analog Data 1 of Input point 1 15 0 Assigned value to Analog Dat...

Page 10: ...tus Generic Status is assigned as Produced I O data by Configurator or Explicit message Assembly Instance ID 107 Data type Byte Data size 5Byte Analog Status of Input point 1 Analog Status of Input point 0 Analog Status of Input point 3 Analog Status of Input point 2 Generic Status 15 0 7 Analog Data Analog Status Analog Data 1 Analog Status is assigned as Produced I O data by Configurator or Expl...

Reviews: