Dimensions
50
3-M4 Tap
60.5
(unit: mm)
105
50
3-Ø4.5
35.3
52
38.5
60.5
●
Panel cut-out
Status LED
(
: ON,
: Flash, : OFF)
No. Type
LED status Color
Descriptions
Troubleshooting
1
MS
Green
Normal operation
I/O communication or message communication is
working.
-
NS
Green
2
MS
Green
Standby of duplicated address
The status of standby for receiving message of
duplicated address check from master unit.
-
NS
-
3
MS
Green
Standby of normal operation
The status of standby for establish connection from
master unit.
-
NS
Green
4
MS
Red
Watchdog timer error
The status that DIP switch or another switch
setting is invalid.
Change the switch with valid
value and re-supply the power.
NS
-
5
MS
Red
Switch setting error
The status that DIP switch or another switch setting
is invalid.
Change the switch setting to valid value
and re-supply the power.
NS
-
6
MS
Red
Changed address during normal operation
The status that address is changed during normal
operation.
Change the initial address at the power
applied at first.
NS
Green
7
MS
Green
Invalid address
The status of setting invalid address
Change the valid address and re-supply
the power.
NS
Red
8
MS
Red
Duplicated address
There is duplicated address in the network.
Occuring Bus-Off error
Communication is stopped with Bus-Off.
Change node address not duplicated.
Power on the slave unit again. Check
master unit, communication, cable,
terminating resistance and noise of
network.
NS
Red
9
MS
Green
I/O Connection time out
Check the master setting and the user
program.
NS
Red
※
Status of MS LED, NS LED