1. DeviceNet connector

 

Unit Descriptions

2

3

4

5

6

1

2.  Rotary switch for node address 

Two rotary switches are used for setting node address.

  

 X10 switch represents the 10’s multiplier and X10 switch represents the 1’s multiplier.

3. Status

 LED

It is LED for displaying Unit status (MS) and Network status (NS).

4. 

Rail Lock

 It is used for mounting DIN rail or with bolt.

5. DIP switch

: It is used for set I/O range. (factory default: all switches are OFF)

ON

1

2

3

4

5 6 7 8

(●: ON, -: OFF)

1:  By turning ON SW8, I/O range is set by DIP switches (SW1 to SW6).  By turning OFF SW8, I/O range is set by communication.  

 When setting I/O range by DIP switches, CH0 and CH1 (CH2 and CH3) cannot be set individually.  

 When setting it by communication, each channel is set individually. 

6.

 

I/O Terminal block: 

It is terminal block for connecting external device I/O. 

No.

Color

For

Organization

5

Red

24VDC (+)

   

V+
CAN_H
SHIELD
CAN_L
V-

4

White CAN_H

3

None SHIELD

2

Blue

CAN_L

1

Black

24VDC (-)

ARD-AI04 (Input model)

ARD-AO04 (output model)

CH0, CH1

CH2, CH3

CH0, CH1

CH2, CH3

I/O range

SW1 SW2 SW3 SW4 SW5 SW6 SW1 SW2 SW3 SW4 SW5 SW6 SW7

SW8

1

0-5VDC

-

-

-

-

-

-

-

-

-

Not supported

Not

supported

(Off Setting) 

ON

Using DIP 

switch

OFF

Not using DIP 

switch

1-5VDC

-

-

-

-

-

-

0-10VDC

-

-

-

-

-

-

-5-5VDC

-

-

-

-10-10VDC

-

-

-

-

-

-

DC4-20mA

-

-

Not supported

-

-

-

DC0-20mA

-

-

-

-

Summary of Contents for ARD-A Series

Page 1: ...esis reading model name and number of units I O and status flag monitoring Built in surge ESD protection Reverse polarity protection circuit Mounting DIN rail method and bolt mounting method I O points I O type Digital Analog Network Item AR D A 04 4 point type A Analog type D 1 Digital type D DeviceNet type AR Autonics Remote I O I Input type O Output type 1 For digital type refer to ARD D Series...

Page 2: ...istance max 600Ω Max allowablerange 5 F S of rated input range 5 F S of rated output range Resolution 14bit 1 16 000 Accuracy At room temperature 25 5 range 0 3 F S Out of room temperature range 0 6 F S Insulation resistance Over 200MΩ at 500VDC megger Noise immunity 240V the square wave noise pulse width 1 by the noise simulator Dielectric strength 500VAC 50 60Hz for 1 min between external termin...

Page 3: ...DIP switches SW1 to SW6 By turning OFF SW8 I O range is set by communication When setting I O range by DIP switches CH0 and CH1 CH2 and CH3 cannot be set individually When setting it by communication each channel is set individually 6 I O Terminal block It is terminal block for connecting external device I O No Color For Organization 5 Red 24VDC V CAN_H SHIELD CAN_L V 4 White CAN_H 3 None SHIELD 2...

Page 4: ...NS Green 4 MS Red Watchdog timer error The status that DIP switch or another switch setting is invalid Change the switch with valid value and re supply the power NS 5 MS Red Switch setting error The status that DIP switch or another switch setting is invalid Change the switch setting to valid value and re supply the power NS 6 MS Red Changed address during normal operation The status that address ...

Page 5: ...ower circuit Output circuit Power circuit V OUT COM I OUT COM Load Max 1KΩ Load Max 600Ω Analog GND Terminating Resistance 120Ω 1 of metallic film 1 4W Do not install terminating resistance on ARD unit or it may cause network problem impedance can be too high or low or malfunction Connect terminating resistance on the both ends of the trunk line Communication Distance Baud Rate Max network length ...

Page 6: ...e to the DeviceNet connector and tighten the fixed bolt of the connector by a driver tightening torque 0 5N m Connect the DeviceNet connector to ARD unit and supply the power to Network PIN No Signal 5 V 4 CAN_H 3 SHIELD 2 CAN_L 1 V PIN No Signal 5 V 4 CAN_H 3 SHIELD 2 CAN_L 1 V Master unit Black ARD unit 5 Red V 4 White CAN_H 3 None SHIELD 2 Blue CAN_L 1 Black V Red White None Blue Setting of mas...

Page 7: ...t You can set the comments for the unit product description on network It can be read by Configurator or Explicit message Set comment by Explicit message at Unit Comment of Application Object Setting range max 32 characters Last maintenance date It saves the last date of maintenance It can be read written by Configurator or Explicit message Set maintenance date by Explicit message at I O Last Main...

Page 8: ...mpling cycle It is able to read write by Configurator or Explicit message It is applied when Moving Average is set as ON at Function Choice of Analog Input Point Set the number of digital filters at Moving Average Filter of Number Setting range 0 to 8 factory default 3 Moving Average No_8 When operating analog input cable voltage current input is disconnected Broken Wire Flag Bit turns ON at Analo...

Page 9: ...a by Configurator or Explicit message By property setting assignment is available as Analog Input Value Peak Value Bottom Value Assembly Instance ID 103 Default 0 Setting range 0 to 2 Analog Input Value 0 Peak Value 1 Bottom Value 2 Data type Word Data size 4Word 0 15 Assigned value to Analog Data 1 of Input point 0 Assigned value to Analog Data 1 of Input point 1 15 0 Assigned value to Analog Dat...

Page 10: ...tus Generic Status is assigned as Produced I O data by Configurator or Explicit message Assembly Instance ID 107 Data type Byte Data size 5Byte Analog Status of Input point 1 Analog Status of Input point 0 Analog Status of Input point 3 Analog Status of Input point 2 Generic Status 15 0 7 Analog Data Analog Status Analog Data 1 Analog Status is assigned as Produced I O data by Configurator or Expl...

Reviews: