background image

Installation & Operation Information 

Non-Electric Dry Chlorine Pellet Feeder

Model 400

Automated Pure Water

Summary of Contents for 400

Page 1: ...Installation Operation Information Non Electric Dry Chlorine Pellet Feeder Model 400 Automated Pure Water ...

Page 2: ...ICE OF THE MODEL 400 FEEDER FOR ANY LOSS DAMAGE OR INJURY TO PERSON OR PROPERTY INCLUDING ANY SUCH LOSS DAMAGE OR INJURY ATTRIBUTABLE TO MANUFACTURER S NEGLIGENCE OR FAULT AND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES from a the design manufacture sale delivery installation repair operation or use of the Model 400 feeder or any part thereof b any actual or alleged failure or defect in the ...

Page 3: ...ter logged pressure tank or air pressure is low or high in the air bag The Model 400 feeder will dispense the same amount of chemical for each cycle of the pump from maximum to minimum pressure When used on a constant pressure and flow it is neces sary to replace the valve No 11 Replace it with the optional adjustable valve No 20 It may be necessary to install the optional screen filters No 19 in ...

Page 4: ...e the fluid if needed The chemical solution out is controlled with the optional rate of feed valve in a constant pressure system To oxidize one PPM of Hydrogen Sulfide H2S it takes 2 2 PPM of Chlorine Cl2 To oxidize 1 PPM of Iron Fe it takes 64 PPM of Cl2 Example If you have 4 PPM of Fe and 1 PPM of H2S look on the vertical portion of the graph labeled PPM and start at 4 and move horizontal to the...

Page 5: ... 12 13 14 15 Approximate Model 400 Feeder Cl2 Concentration Per Pump Cycle for a 42 Gallon Pressure Tank 1 2 PPM A 3 5 PPM 2 8 PPM B 13 PPM 3 30 PPM C 40 PPM OFF 60 PPM If Using an 82 Gallon Pressure Tank Divide the PPM By 2 If Using a 20 Gallon Pressure Tank Multiply the PPM By 2 CHLORINE Cl2 PPM I R O N F e x 6 4 C l 2 HYDROGEN SULFIDE H2S x 2 2 Cl2 ...

Page 6: ...umber or letter directly under it as per figure 1 The hole in the tube should show in the center of the hole in the cap Hole Settings in Parts Per Million CBA 3 2 1 UNIT MUST BE INSTALLED AFTER THE PRESSURE TANK CAUTION When Draining Chlorine Chlorine Can Bleach Clothing May Burn Eyes Skin PVC BALL VALVE DRAIN VALVE TO RELIEVE PRESSURE AND DRAIN UNIT 400 FEEDER PVC BALL VALVE U S PATENT NOS 5 053 ...

Page 7: ...ot add water to the unit or operation will be inhibited It may take a few pump cycles before chlorine is dispensed 6 Replace top No 4 and close drain valve 7 Tum on water NOTES If unit is opened after pressurization it is neces sary to drain fluid to the bottom of cap No 7 before repressurizing or operation will be inhib ited If unit is used for odor removal do not refill until odor returns to min...

Page 8: ... a smaller tank such as a 20 gallon tank cut the chlorine output by one half The Model 400 feeder will output the same amount of chemical for each pump cycle and a smaller tank is delivering less water on each pump cycle increasing the chemical concentration High odor and or Unit appears not to be dispensing the proper amount of chemical 1 Unit needs chlorine or it is over filled Max 3 4 full 2 Wr...