If you need the SE6166's serial number when troubleshooting, the number is on:
•
a sticker on the back of the main controller board
•
a Module Status report (Modstat) under
Core
(or
Main
)
board hardware
To obtain a modstat in WebCTRL:
1
Select the SE6166 in the
NET
tree.
2
On the
Properties
page, click
Module Status
.
The SE6166's 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of
data retention during power outages.
If the SE6166 sends a Low Battery alarm to WebCTRL, replace the battery.
1
Remove the battery from the controller, making note of the battery's polarity.
2
Insert the new battery into the controller, matching the polarity of the battery you
removed.
3
Download the SE6166.
If needed for troubleshooting or start-up, you can prevent WebCTRL Server from
communicating with the SE6166.
1
Select the SE6166 in WebCTRL's
NET
tree.
2
On the
Properties
page, select the
Out of Service
checkbox.
3
Click
OK
.
Serial number
Replacing the
SE6166's
battery
To take the