SE6166 Controller • Rev. 4/13/2011
13
© 2011 Automated Logic Corporation
To use an input or output, you must assign it to its corresponding point in the control
program.
1
In WebCTRL's
GEO
tree, select the equipment controlled by the SE6166.
2
On the
Properties
page, select the
I/O Points
tab.
3
In each point's
Num
field, type the number of the controller's corresponding input or
output. For example, if you use DO1 on the SE6166 for the point
Fan S/S
, type
1
in
the
Num
field for
Fan S/S
.
NOTES
○
Exp
(expander number) is 00 for the SE6166.
○
Do not assign the same output number to more than one point.
4
Enter the appropriate values for each input and output in the remaining columns. See
Input values
,
Output values
,
Resolution values
and
Offset/Polarity values
below.
NOTE
You can also enter these values in EIKON LogicBuilder.
5
If you have not performed the initial download to the SE6166, you must download
now so you can verify inputs and outputs.
6
To verify each input's operation, force each sensor to a known value, then compare it
to the
Value
shown on the
Properties
page on the
I/O Points
tab.
7
To verify each output's operation, lock each output to a known condition on the
I/O
Points
tab, then verify that the equipment operates correctly.
Input
I/O Type
Sensor/Actuator Type
Min/Max
Analog (BAI)
0-5 Vdc
0–5 Volt
Linear Full Range
Engineering values
associated with 0 Vdc
(Min) and 5 Vdc (Max)
1
0-10 Vdc
0–10 Volt
Linear Full Range
Engineering values
associated with 0 Vdc
(Min) and 10 Vdc (Max)
1
2-10 Vdc
0–10 Volt
Linear w/Offset,
2–10 Volts
Engineering values
associated with 2 Vdc
(Min) and 10 Vdc (Max)
1
0-20 mA
0–20 mA
Linear Full Range
Engineering values
associated with 0 mA
(Min) and 20 mA (Max)
1
4-20 mA
0–20 mA
Linear w/Offset,
4–20 mA
Engineering values
associated with 4 mA
(Min) and 20 mA (Max)
1
RTD
RTD Input
Select your RTD type or set
up and select a
Non-Linear,
Custom Table
2
N/A
To assign inputs or outputs to points
Input values