SE6166 Controller • Rev. 4/13/2011
21
© 2011 Automated Logic Corporation
5
Type the computer's
Port
number that the USB cable is connected to.
NOTE
To find the port number, plug the USB cable into the computer's USB port, then
select
Start
>
Control Panel
>
System
>
Hardware
>
Device Manager
>
Ports (Com &
LPT)
. The COM port number is beside
CP210x USB to UART Bridge Controller
.
6
Set the
Baud
rate to 115200.
7
Click
OK
.
8
On the
View
tab, click the drop-down arrow next to your device's network
Connection
,
then select
BACnet Local Access
.
9
Click
OK
.
10
On the
Configure
tab, select
BACnet Local Access
, then click
Start
.
NOTE
If WebCTRL displays an error, make sure the COM port you selected is not in
use. For example, PuTTY may be open and is holding the port open.
11
On the
NET
tree, select the controller that you are connected to.
12
Click the menu button
, then select
Manual Command
.
13
Type
rnet here
in the dialog box, then click
OK
.
14
On the
Properties
page, click
Module Status
. If WebCTRL displays a Modstat report,
WebCTRL is communicating with the controller.
If you have problems mounting, wiring, or addressing the SE6166, contact ALC Technical
Support.
If you cannot communicate with a controller after downloading it, as a last resort, you can
manually format the controller to erase its memory.
1
Turn
off
the SE6166's power. Make sure the address switches are not set to 0, 0.
2
Hold down the controller’s
Format
button while you turn its power on.
3
Continue to hold down the
Format
button until the
Error
LED stops flashing and turns
on, then release the button.
4
Download the SE6166.
Troubleshooting
Formatting the
controller