SE6166 Controller • Rev. 4/13/2011
16
© 2011 Automated Logic Corporation
You can control a digital output using the
Auto-Off-On
switch.
If switch position is...
Normally open output contacts are...
Auto
Determined by control program
Off
Locked open
On
Locked closed
The control program can monitor the status of an
Auto-Off-On
switch and display the
status on the control program's
Point Checkout
page in WebCTRL. The
Value
of the point
monitoring the
Auto-Off-On
switch shows
Off
if the switch is set to
Auto
, and
On
if the
switch is set to
Off
or
On
.
To monitor an Auto-Off-On switch
1
Insert a BACnet Binary Input microblock in the control program.
2
On the microblock's
Properties
page in WebCTRL, set the
I/O Type
field to
H-O-A
Status Feedback
.
3
In the
Input Number
field, type the number of the output you want to monitor.
After you download the driver and control program(s) to the SE6166, you may want to
change the driver's properties to suit your application.
1
On WebCTRL's
NET
tree, click to the left of your SE6166.
2
Click to the left of
Driver
to see its children.
3
Make changes as needed on the
Properties
page for
Driver
and any of its children.
On the
Driver
page, you can change the following properties:
•
BACview inactivity timeout and user password. See table below.
•
Module clock synchronization and failure. See table below.
•
Network Input microblock communication properties.
BACview Control
Overwrite Daylight Saving
parameters set in
BACview?
Yes
—Every download includes Daylight Saving Time
properties from System Settings page and overwrites
changes to these properties made from BACview.
No
—Download System Settings page Daylight Saving Time
properties during first download. You must make
subsequent changes from BACview. (Primarily for OEM use.)
To use the Auto-
Off-On switches
To set up the driver