SE6166 Controller • Rev. 4/13/2011
9
© 2011 Automated Logic Corporation
4
Set the appropriate jumpers on the SE6166.
To use...
For...
Any input
Thermistor
Dry contract
0–5 Vdc
0-10 Vdc
0–20 mA
RTD
Set each input's
Universal Input Mode
Select
jumper to the type
of signal the input will
receive.
Jumpers for
inputs...
1
3
5
7
9
11
13
15
2
4
6
8
10
12
14
16
Aux Power Out
connector
Loop-powered
4-20 mA
Set the
Select
jumper to
+5V
or
+24V
as
required by the sensor.
5
Connect the digital output wiring to the screw terminals on the SE6166 and to the
controlled device.
24 Vac/dc
Motor
Valve
Any DO
Any DO
Any DO