Using a computer and a USB Link Kit, you can communicate locally with the SE6166 to
download or to troubleshoot.
PREREQUISITES
•
A computer with a USB port
•
A USB Link Kit. See the
USB Link Kit Technical Instructions
The USB Link Kit driver is installed with WebCTRL v5. But if needed, you can
get the latest driver from http://accounts.automatedlogic.com/download. Install the
driver before you connect the USB Link Kit to your computer.
•
v1.70 or later controller driver
CAUTION
If multiple controllers share power but polarity was not maintained when they
were wired, the difference between the controller's ground and the computer's AC power
ground could damage the USB Link Kit and the controller. If you are not sure of the wiring
polarity, use a USB isolator between the computer and the USB Link Kit. Purchase a USB
isolator online from a third-party manufacturer.
Connect the USB Link Kit to the computer and to the controller's Local Access port.
Connect to
computer’s
USB port
Connect to
the Local
Access port
USB Link Kit
NOTE
If using a USB isolator, plug the isolator into your computer's USB port, and then
plug the USB Link Kit cable into the isolator.
To communicate in WebCTRL, do the following:
1
On WebCTRL's
CFG
tree, select
Connections
.
2
On the
Configure
tab, click
Add
.
3
From the
Type
drop-down list, select
BACnet Local Access
.
4
Optional: Edit the
Description
.
To communicate through the local access port
To set up a
Local Access
connection in
WebCTRL