2 Flame Safeguard
Page | 64
MM Application Possibilities
2.8.3 No Air Servomotor
Some burner applications use natural draught to supply air for combustion without the need for air
blower for forced draught and there is no air damper, so the air supplied to the burner is at
atmospheric pressure. In such applications there is no need for control on the air channel and only the
fuel channel requires controlling.
The Mini Mk8 MM allows the system to be set so that the burner is commissioned with channel 1
servomotor only to control the fuel flow. This configuration can also be used for pre-mix burners
where the fuel to air volume ratio is not varied. In these applications, channel 1 is sued to vary the
volume of combined air and fuel.
The gas servomotor is wired as normal to the MM, and option 4 must be set to ‘No Air Channel.’
Option 8 must be set to ‘Channel 1 only.’
Figure 2.8.3.i Commissioning No Air Servomotor
The commission procedure follows the normal steps but with channel 1 servomotor only.
For more information on using the Mini Mk8 MM on an atmospheric burner or pre-mix burner and
what limit switches or purge delay is required, please contact Autoflame Engineering Ltd.
Summary of Contents for Mk8 MM
Page 1: ...Combustion Management Systems MM APPLICATION POSSIBILITIES Technical Manual 18 12 2019...
Page 8: ...1 Sensors Page 2 MM Application Possibilities Gas Pressure Sensor...
Page 27: ...1 Sensors Page 21 MM Application Possibilities Air Pressure Sensor...
Page 32: ...1 Sensors Page 26 MM Application Possibilities Steam Pressure Sensor...
Page 36: ...1 Sensors Page 30 MM Application Possibilities Outside Temperature Sensor...
Page 37: ...1 Sensors Page 31 MM Application Possibilities Outside Temperature Module...
Page 38: ...1 Sensors Page 32 MM Application Possibilities Outside Temperature Module Wiring...
Page 42: ...2 Flame Safeguard Page 36 MM Application Possibilities 2 1 1 Interrupted Pilot Gas...
Page 43: ...2 Flame Safeguard Page 37 MM Application Possibilities 2 1 2 Interrupted Pilot Oil...
Page 46: ...2 Flame Safeguard Page 40 MM Application Possibilities IR End View Scanner...
Page 72: ...2 Flame Safeguard Page 66 MM Application Possibilities 2 9 3 Wiring...
Page 81: ...5 Intelligent Boiler Sequencing Page 75 MM Application Possibilities 5 1 3 Hot Water Example...
Page 83: ...5 Intelligent Boiler Sequencing Page 77 MM Application Possibilities 5 1 5 IBS Communications...