1 Sensors
Page | 20
MM Application Possibilities
1.3
Air Pressure Sensor
IP
65
NEMA
14
Housing & Lid
Aluminium
Power Consumption 0.1 Watts
Mounting
Breather hole to be piped or used as differential pressure for IP65/NEMA 4
Installation
Sensor should be installed vertically
Operating Temp.
-25
O
C to 85
O
C (-13
O
F to 185
O
F)
Part No.
Min. Pressure
Max. Pressure
Zero Range
mbar
“wg PSI mbar
“wg PSI
mbar
“wg
PSI
MM80005
Digital
-68
-27
-1
68
27
1
-1.36 to 1.36
-0.54 to 0.54
-0.02 to 0.02
Analogue
-0.75
0.3
0
65
25
1
-2.5 to 1.25
-1.0 to 0.5
-0.02 to 0.02
MM80013
Digital
-137
-55
-2
137
55
2
-2.74 to 2.74
-1.1 to 1.1
-0.04 to 0.04
Analogue
-1.5
0.6
0
130
50
2
-5.0 to 2.5
-2.0 to 1.0
-0.04 to 0.04
Digital - when used with Mk8 MM, Mini Mk8 MM and Mk8 DTI
Analogue - when used with Mk7 MM
Air Sensor Mk8 MM Mini Mk8 MM
Brown
T31
T29
Purple
T32
T30
Blue
T33
T48
Red
T34
T49
Connect screen at only one end.
Drawing No. 9005
Socket
Plug
Circuit board
Pressure
switching unit
Sealing O-rings
1/8” NSP Nylon
plug with
breather hole
Quick connection
screened flying
lead (1.5m)
Plug
¼” Tapered male
nipple
Summary of Contents for Mk8 MM
Page 1: ...Combustion Management Systems MM APPLICATION POSSIBILITIES Technical Manual 18 12 2019...
Page 8: ...1 Sensors Page 2 MM Application Possibilities Gas Pressure Sensor...
Page 27: ...1 Sensors Page 21 MM Application Possibilities Air Pressure Sensor...
Page 32: ...1 Sensors Page 26 MM Application Possibilities Steam Pressure Sensor...
Page 36: ...1 Sensors Page 30 MM Application Possibilities Outside Temperature Sensor...
Page 37: ...1 Sensors Page 31 MM Application Possibilities Outside Temperature Module...
Page 38: ...1 Sensors Page 32 MM Application Possibilities Outside Temperature Module Wiring...
Page 42: ...2 Flame Safeguard Page 36 MM Application Possibilities 2 1 1 Interrupted Pilot Gas...
Page 43: ...2 Flame Safeguard Page 37 MM Application Possibilities 2 1 2 Interrupted Pilot Oil...
Page 46: ...2 Flame Safeguard Page 40 MM Application Possibilities IR End View Scanner...
Page 72: ...2 Flame Safeguard Page 66 MM Application Possibilities 2 9 3 Wiring...
Page 81: ...5 Intelligent Boiler Sequencing Page 75 MM Application Possibilities 5 1 3 Hot Water Example...
Page 83: ...5 Intelligent Boiler Sequencing Page 77 MM Application Possibilities 5 1 5 IBS Communications...