1 Sensors
Page | 15
MM Application Possibilities
1.1.3 Calculating Proving Time and Pressure Change
The following formulae may be used for calculating the proving time and pressure change allowed.
They are based on DVGW requirements of a leakage rate of 0.1% of the maximum volume flow.
Valve Proving Time:
𝑉𝑉𝑉𝑉𝑉𝑉
= 4 ×
��
𝑙𝑙𝑉𝑉
×
𝑃𝑃𝑃𝑃
𝑀𝑀𝑉𝑉𝑉𝑉
÷ 1000
�
+ 1
�
Vpt
Valve proving time in seconds.
Ip
Inlet pressure in millibars.
Pv
Pipe
volume in litres (volume = πr
2
x length, total volume of any interconnecting
pipe between valve seals)
Mtp
Maximum gas throughput in litres per hour.
Pressure change:
𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃
𝑐𝑐ℎ𝑎𝑎𝑎𝑎𝑎𝑎𝑃𝑃
= 0.25 ×
𝑁𝑁𝑁𝑁𝑁𝑁𝑁𝑁𝑎𝑎𝑎𝑎𝑙𝑙
𝑁𝑁𝑎𝑎𝑙𝑙𝑃𝑃𝑉𝑉
𝑉𝑉𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃
(
𝑁𝑁𝑚𝑚𝑎𝑎𝑃𝑃
)
Example
Valve proving time:
Inlet pressure = 50mBar
Pipe volume = 5litres
Max gas flow = 100,000litres per hour
𝑉𝑉𝑉𝑉𝑉𝑉
= 4 ×
��
50 × 5
100,000 ÷ 1000
�
+ 1
�
𝑉𝑉𝑉𝑉𝑉𝑉
= 14
𝑃𝑃𝑃𝑃𝑐𝑐𝑃𝑃
Set option 132 = 15 seconds.
Set parameter 132 = 15 seconds.
Note:
option 132 is set in increments of 5 seconds, values must be rounded up.
Pressure change:
Inlet pressure = 50mBar
𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃
𝑐𝑐ℎ𝑎𝑎𝑎𝑎𝑎𝑎𝑃𝑃
= 0.25 × 50
𝑁𝑁𝑚𝑚𝑎𝑎𝑃𝑃
Set Option/Parameter 133 = 12.5 mBar
Note:
This is a metric formula, therefore imperial units must be converted before applying this calculation.
To convert PSI to mBar multiply the PSI value by 68.94.
To convert Cubic Feet to Litres multiply the Cubic Feet value by 28.31.
To convert Cubic Feet per hour to Litres multiply your Cubic Feet per hour value by 28.31.
Summary of Contents for Mk8 MM
Page 1: ...Combustion Management Systems MM APPLICATION POSSIBILITIES Technical Manual 18 12 2019...
Page 8: ...1 Sensors Page 2 MM Application Possibilities Gas Pressure Sensor...
Page 27: ...1 Sensors Page 21 MM Application Possibilities Air Pressure Sensor...
Page 32: ...1 Sensors Page 26 MM Application Possibilities Steam Pressure Sensor...
Page 36: ...1 Sensors Page 30 MM Application Possibilities Outside Temperature Sensor...
Page 37: ...1 Sensors Page 31 MM Application Possibilities Outside Temperature Module...
Page 38: ...1 Sensors Page 32 MM Application Possibilities Outside Temperature Module Wiring...
Page 42: ...2 Flame Safeguard Page 36 MM Application Possibilities 2 1 1 Interrupted Pilot Gas...
Page 43: ...2 Flame Safeguard Page 37 MM Application Possibilities 2 1 2 Interrupted Pilot Oil...
Page 46: ...2 Flame Safeguard Page 40 MM Application Possibilities IR End View Scanner...
Page 72: ...2 Flame Safeguard Page 66 MM Application Possibilities 2 9 3 Wiring...
Page 81: ...5 Intelligent Boiler Sequencing Page 75 MM Application Possibilities 5 1 3 Hot Water Example...
Page 83: ...5 Intelligent Boiler Sequencing Page 77 MM Application Possibilities 5 1 5 IBS Communications...