Installation and operation manual
IM-S2-UX-EN-V1.4
31
8.
Maintenance
CAUTION! Do not touch the heat sink when the inverter is in operation. Turn OFF the inverter
(see section 5.5) and allow for cooling down before cleaning.
CAUTION! Never use any solvents, abrasives or corrosive materials to clean the inverter.
The UX series inverters require general maintenance to be performed once per year. Impurities such as dust and
dirt accumulation on the heat sink may negatively affect the inverter’s ability to dissipate heat. Any dirt or dust
can be removed with a cloth or soft brunch.
8.1
Fan Maintenance
If the fan does not work properly, the inverter will not be cooled effectively and inverter efficiency may be
reduced.
Note: The S2.UX40000(S) and S2.UX50000(S) have two fans, the S2US60000(S) has three fans.
Broken fans should be replaced following process below:
1.
Disconnect the AC power.
2.
Turn the DC switch to "OFF" position.
3.
Wait for 10 minutes at least.