Installation and operation manual
IM-S2-UX-EN-V1.4
17
NOTE: There is no need to connect N to AC side for the UX series three-phase inverter,
the ground wire can be connected to the grounding hole on the right side of the inverter
heat sink.
Cable specification
Copper-cored
cable
Copper clad
aluminum /
Aluminum Alloy
cable
Traverse cross sectional area (mm
2
)
Range
16~35
25~35
Recommended
25
35
Cable outer diameter (mm)
Range
22~32
Recommended
27
NOTE: Prepare M6 OT terminals
The steps to assemble the AC grid terminals are listed as follows:
A)
Strip the end of AC cable insulating jacket about 90mm then strip the end of each wire (as shown in figure
5.17).
Figure 5.17 Strip AC cable
NOTE: L2 (insulation stripping length) is 2mm-3mm longer than L1 (OT cable terminal
crimping area)
B)
Strip the insulation of the wire core, insert into the cable crimping area of the OT terminal, then use a
hydraulic crimp tool to crimp it firmly. The wire must be covered with heat shrinkable tube or insulating tape.
When using the heat shrinkable tube sleeve the heat shrinkable tube over the wire before crimping the OT
terminal.
C)
Remove the 4 screws on the AC terminal cover and remove the cover.
L2
L1