9
Assembly Instruction
KS 4 S12 24V DC R
D
ATA
SHEET
KS4 S12 24V DC R
A
UMÜLLER
chain drives have an integrated cable routing with connection sockets on both housing ends.
This enables the following options:
• Universal plug with various cabel lengths
Part.-No.:
501250
- 1 m cable length /
501258
- 2 m cable length /
501251
- 3 m cable length /
501252
- 5 m cable length /
501253
- 10 m cable length
• Series connection of several drives into multi drive systems
• Pover supply from both sides
S
L
235
15
5
35
24
R
(Right)
O
PTION
TECHNICAL DATA
U
N
Rated voltage
24V DC (± 20 %), max. 2 Vpp
I
N
Rated current
0,9 A
I
A
Cut-off current
1,2 A
P
N
Rated power
22 W
ED
Duty cycle
30 % (ON: 3 min. / OFF: 7 min.)
Protection rating
IP 32
Ambient temperature range
min. -5 °C ... +75 °C
F
Z
Pulling force max.
400 N
F
A
Pushing force
s > 600 mm only for pulling application
F
H
Pullout force
1.800 N (fastening depended)
Chain
Stainless steel, without protruding rivet heads.
Simple connection to casement brackets.
Small bending radii allow maximum opening angles
of small windows.
Connecting cable
non-halogen, grey 5 x 0,5 mm², ~ 2 m
v
Speed
s < 400
8,0 mm/s
8,0 mm/s
s 500 – 600
12,0 mm/s
8,0 mm/s
s > 600
13,5 mm/s
8,0 mm/s
s
Stroke
200 – 800 mm (± 5 %)
L
Length
see order data
Feedback contact
limit position „CLOSE“ (max. 24 V, 500 mA)
Sound pressure level A
70 dB (A)
50
100
250
150
200
300
350
400
F
Zug
Pull
Schub
Push
(N)
S
(mm)
0
500
600
700
800
400
300
200
Application: natural ventilation, SHEV, ferralux®-NSHEV
Internal intelligent cut-off switch S12
Feedback limit position „CLOSE“ (max. 24V, 500 mA)
Equipment:
Additional universal plug set for multi-drive operation
Options
Programmable special functions
Programmable feedback limit position „OPEN“ (max. 24V, 500 mA)
M-COM for automatic synchronised run of multi drive systems and automatic sequence
control with FV locking drives (S3/S12 SW V2)
D
ATA
SHEET
02