22

Installation instruction 

RWA - Control Unit EMB 7300

i

ndiCAtoR

 

And

 C

ontRol

 

ElEMEnts

Position in the Control Unit

Meaning of the Displays (overview)

The indicators and control elements (switches) are in the 
same position on all EMB 7300 versions. 
Only the number of ventilation lines varies. 
The versions EMB 7300 5A-0102, EMB 7300 10A-0102, 
EMB 7300 20A-0102 have two sets of indicators and 
control elements for the drive control (LT 1 and LT 2). 

Basically, the green indicator „

B

“ signals that the Con-

trol Unit works properly. A yellow indicator „

S

“ lighting 

up signals a fault to be eliminated immediately.
Since the type of fault signal into the breakglass units 
may differ from the fault indicator „

S

“ in the Control 

Unit, always pay regard to the indicators in the Control 
Unit for exact troubleshooting.

07

i

nDiCator

 

anD

 C

ontrol

 e

lements

Notes

GN  = green
YE  = yellow
RD  = red

only available on Control Unit version
EMB 7300   5A-0102
EMB 7300 10A-0102
EMB 7300 20A-0102

A

S

B

Push buttons:

Drive run direction 

A

 = OPEN / 

Z

 = CLOSE

(2 x on version 0102)

Reset / EMERGENCY-CLOSE
(resetting smoke detectors  
after EMERGENCY-OPEN)

1 32 33 35 36 37

1

1

1

2

2

5

7

1

1 13 14 15 16 17 18 19

A

S

B

A

Z

A

Z

1 32 33 35 36 37

A

Z

A

Z

1

1

2

2

3

3

1 72

US

B

1.REL65

2.REL65

BUS-Module

BUS

Wind

Rain

RM

HSE

LT 2

F1

A+

A-

N+

N-

Drive 1

Steck

er für

Fr

ont-Button

Drive 2

A

Z

Reset

LT 1

Indicators:

(GN) = Operation
(YE)  = Fault
(RD) = Alarm (EMERGENCY-OPEN)

Drive run direction and position

A

 = OPEN (RD) / 

Z

 = CLOSE (GN)

Drive run direction

A

 = OPEN (RD) / 

Z

 = CLOSE (GN) (Duo-LED)

(2 x on version 0102). The Duo-LED displays
the current switched direction of the line vol-
tage for the duration of the drive run time.

A

Z

A

S

B

Faults

Indicator

Meaning

Note

Power failure / 
accumulator operation

Accumulator fault

Breakglass unit fault

Smoke detector fault

Service required

Licence software  
required for setting

Fault bus module
(e.g. radio module)

Fault 
drive line 1

Fault 
drive line 2

only on Control Unit 
version 0102

Fault EMERGENCY- 
CLOSE button

Persistent contact

System was closed via 
breakglass unit, smoke  
detectors are still activated.

Drive run direction

Drives

Drives

*) The Duo-LED only lights up for the duration of the drive run time.

A

S

B

A

S

B

5 x blinking

off

slow blinking

on

A

S

B

4 x blinking

off

A

S

B

2 x blinking

off

A

S

B

slow blinking

off

A

S

B

on

off

A

S

B

fast blinking

off

A

S

B

flashes

off

OPEN

CLOSE

off

on (RD)

RD *)

GN *)

A

Z

A

Z

A

Z

1 2 3

on (GN)

off

A

Z

1 2 3

Störung

Alarm activation / EMERGENCY-OPEN

Mains operation

Accumulator operation 
(power failure)

EMERGENCY-OPEN

EMERGENCY-OPEN

flashes (YE)
on (RD)

off

A

S

B

on (RD)

on (GN)

A

S

B

6 x blinking

off

out (YE)

A

S

B

A

S

B

3 x blinking

off

Summary of Contents for EMB 7300

Page 1: ...g to EN12101 10 and control panel according to prEN12101 9 RWA Control Unit EMB 7300 2 5 A 5 A 10 A 20 A tested electrical control device EMB 7300 with recognition number G 514001 Installation and Commissioning Instructions ...

Page 2: ...Maximal detector in drive line Installation step 3 Connection of automatic and manual smoke detectors Installation step 4 Connecting wind and rain sensors Installation step 5 Installing relay plug in card REL and BUS connection Installation step 6 Connecting power supply Installation step 7 System configuration using software EMB Kompakt Installation step 8 Enabling operation completing installati...

Page 3: ... V Volts PU Packaging Units Vpp Residual ripple Voltage Peak Peak W Watts Ω k Ω Ohm Kilohms Figures AC Alternating current 50Hz 60Hz DC Direct current I Electric current L Length ME Module space unit 1 ME 23 mm NC Contact closed normally closed NO Contact opened normally opened P Electric power R Electrical resistance U Electric voltage Um Change over switch Colour abbreviation according to IEC 60...

Page 4: ... lives and protect property Furthermore the electric window ensures fresh air supplied for natural ventilation of the building Intended use according to the Declaration of Con formity The control device is intended for stationary installation and electrical connection as part of a building In accordance with the attached Declaration of Con formity the control device in combination with electromoti...

Page 5: ...e each intervention in the Control Unit of the system Clamping points must be checked for tightness of threa ded connections and cable ends Access to junction boxes clamping points and external drive control systems must be ensured for maintenance work Commissioning operation and maintenance After the installation and after each modification in the set up all functions must be checked with a trial...

Page 6: ...issue of a Declaration of Conformity according to European guidelines The prerequisites of the system see chapter Systems confi guration of software must be checked prior to installation The Software clause for handing over the standard soft ware as part of shipments of the ZVEI German Electrical and Electronic Manufacturer s Association is accepted as legally binding upon installation See our hom...

Page 7: ...ance free back up accumulators 2x 12 V 2 3 Ah Part No 541000 Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24V DC voltage suitable for staircases TECHNICAL DATA Rated values Operating voltage 230V AC 195 253 V AC 50 60 Hz Max power consumption 460 W Output voltage 24V DC 20 28 V DC 0 5 Vpp Output current 5 0 A Ambient temperature range 5 C 40 C Prot...

Page 8: ...ting steel sheet RAL 7035 light grey Dimensions WxHxD 400 x 300 x 150 mm Connection terminals 1 5 mm Drives 6 mm rigid wire Motherboard 1 RWA group 2 Vent groups Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24V DC voltage suitable for staircases TECHNICAL DATA Rated values Operating voltage 230V AC 195 253 V AC 50 60 Hz Max power consumption 805 W ...

Page 9: ...5 x 285 x 122 mm Version 2 5A 5A 400 x 300 x 150 mm Version 10A 400 x 400 x 200 mm Version 20A Preparing assembly Technical Data Warning Important instructions for safe assembly Fully observe all instructions incorrect assembly may lead to serious injuries Before starting the installation please check with the delivery note that the delivery is complete and correct any complaints received later ca...

Page 10: ... exhausting natural ventilation Input for ventilation line 1 max 10 vent buttons Output for drive line 2 only for EMB 7300 5 A 0102 10 A 0102 20 A 0102 Input for ventilation line 2 max 10 vent buttons only for MB 7300 5 A 0102 10 A 0102 20 A 0102 Housing of Control Unit with or without integrated break glass unit and ventilation button Connections for wind and rain sensor disabled in case of alarm...

Page 11: ...ine length and cross section A drives depend on the type of drive and on the number of drives Line length and cross section can be determined according to the following formula Formula to calculate the required wire cross section of a infeed line A cross section of line in mm2 L line length in m I current of connected drives in A U line voltage drop 2 V DC total length infeed line voltage drop Bef...

Page 12: ... 5 A nominal current EMB 7300 10 A max 10 A nominal current EMB 7300 20 A 2x max 10 A nominal current RWA release in case of fire overrides ventilation No ventilation in the event of a mains power supply failure accumulator operation RWA release in case of fire overrides ventilation No ventilation in the event of a mains power supply failure accumulator operation Automatic ventilation control e g ...

Page 13: ...ance with applicab le legal requirements The terminal cross section for the drive connection is EMB 7300 0101 max 2 5 mm flexible EMB 7300 0101 T max 4 0 mm rigid wire EMB 7300 0101 max 4 0 mm flexible EMB 7300 0101 T or EMB 7300 0102 max 6 0 mm rigid wire EMB 7300 0101 EMB 7300 0102 EMB 7300 0102 2 5A 2 5A 5A 5A 5A 10A 10A 20A Formula to calculate the required wire cross section of a infeed line ...

Page 14: ...nection of automatic and manual smoke detectors 04 OK 11 10 9 8 7 6 5 4 3 2 1 1 1 1 22 5 71 1 13 14 15 16 17 18 19 A S B 1 72 OK 11 10 9 8 7 6 5 4 3 2 1 10 k IN C O M O UT IN C O M O UT IN C O M OU T BMA 1 2 3 4 5 1 22 1 22 COM OUT IN IN IN OUT OUT COM COM RE 1 13 14 15 16 18 19 1 2 3 4 5 6 7 8 9 10 11 2 5 A 5 A 20 A 10 A Automatic smoke detector Breakglass unit Buttons Indicators COM Indicators m...

Page 15: ... rain sensors is deactivated Before mounting and positioning the wind rain sen sors carefully read the safety and assembly instructions provided with the products They are part of the system documentation and must be adhered to and kept accor dingly e g for servicing purposes Installation step 4 Connecting wind and rain sensors 2 5 A 5 A 20 A 10 A Installation step 4 Connecting Wind and Rain Senso...

Page 16: ... installation an connect when disconnected from the mains power supply Switch off power supply and secure against reconnection The motherboard has two slots for using one relay plug in card REL 65 each order no 650200 so that external processing of messages via floating relay contact 1 x change over switch 42 V max 0 5 A is possible Cable installation must be in compliance with applicable legalreq...

Page 17: ... AC 50 60 Hz On the version with front mounted push button the connector may be removed Routing via external fuse and switching component PE BU BU BU 2 x back up accumulator 2 3 Ah 12V Ensure correct polarity when connecting red blue Attachment of the accumulators with the optional accumulator holder set Part No 683250 only for compact housing The accumulator set may also be fastened to the housin...

Page 18: ... A N N 1 72 N L V VGG N L USB Do not remove cover F1 F2 F3 Switching power supply 5A RD RD RD RD RD L L Cover SMOKE VENT N N 225 mm 400 mm 285 mm 300 mm 10 A oder 400 mm 20 A Wiring duct 230V AC 50 60 Hz 230V AC 50 60 Hz Version 0102 only Routing via external fuse and switching component Routing via external fuse and switching component PE PE BU BU BU BU Output DC 24V Switching power supply 10 A o...

Page 19: ...free version of the system software version VIEW can be downloaded from the homepage www aumueller gmbh de The software can be installed on a computer notebook or net book Please pay regard to the hardware and system requirements see below Follow the instructionsdisplayed on the screen to install the program The software offers many features to adapt the system to your requirements However you sho...

Page 20: ...s RWA systems require a logbook in which all important master data have to be entered prior to operation enable and all operational events during the period in operation The logbook is part of the system documents and must be stored and available to authorized staff at all times We advise to perform an insulation measurement of the cable network before enabling operation of the plant and to keep a...

Page 21: ...ght open circuit or short circuit in manual fire alarm faulty power monitoring Indicator S blinks slowly open circuit or short circuit in smoke detector line faulty power monitoring Indicator S blinks 2 times service required indicator B green lights up Indicator S blinks 3 times fault bus module e g radio module Indicator S blinks 4 times open circuit or short circuit in drive line 1 faulty power...

Page 22: ... 1 7 2 USB 1 REL65 2 REL65 BUS Module BUS Wind Rain RM HSE LT 2 F1 A A N N Drive 1 Stecker für Front Button Drive 2 A Z Reset LT 1 Indicators GN Operation YE Fault RD Alarm EMERGENCY OPEN Drive run direction and position A OPEN RD Z CLOSE GN Drive run direction A OPEN RD Z CLOSE GN Duo LED 2 x on version 0102 The Duo LED displays the current switched direction of the line vol tage for the duration...

Page 23: ... contract with a specialist company authorized by the manufacturer A sample maintenance contract can be downloaded from the homepage of Firm Aumüller Aumatic GmbH www aumueller gmbh de After opening of the system housing voltage carrying parts are exposed Each time before performing main tenance work or making a modification of the structure e g replacement of the window drive the mains voltage an...

Page 24: ...wing Improper use of the product Improper installation commissioning operation maintenance or repair of the product Operating the product by defect and improper installed or not functioning safety and protection devices Ignoring instructions and installation requirements in these in structions Unauthorized constructional modifications at the product or accessories Disaster situations due to effect...

Page 25: ...25 Installation instruction RWA Control Unit EMB 7300 08 ...

Page 26: ... different Control Unit versions Remark Terminals Drive 1 Drive 2 only version 0102 CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE ZU Operation Fault COM COM OPEN OPEN OPEN OPEN OPEN OPEN Buttons Buttons Buttons Indicators Indicators Indicators EMERGENCY EMERGENCY OPEN OPEN COM Line monitoring Line monitoring COM COM COM COM COM only version 0102 optional optional Ventilation 1 Ventilation 2 1 REL 65 2 REL 6...

Page 27: ...rvices The publication of these assembly and commissioning instructions supersedes all previous editions The VdS approval includes the following Control Units EMB 7300 without RWA button EMB 7300 with orange RWA button EMB 7300 without RWA button EMB 7300 with orange RWA button EMB 7300 EMB 7300 2 5A 2 5A 5A 5A 10A 20A Certificate and Declaration of Conformity We declare under our sole responsibil...

Page 28: ...en Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000017000_V0 1_KW05 14 www aumueller gmbh de AUMÜLLER AUMATIC GMBH Gemeindewald 11 86672 Thierhaupten Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000007401_V2 4_KW46 20 ...

Reviews: