15
Installation instruction
RWA - Control Unit EMB 7300
Connecting wind and rain sensors
The system software offers the option to adapt the
response threshold of the wind sensor to the local con-
ditions. The factory default setting is 5 m/s. Further
modifications of the standard configuration require a
paid licence for the software.
Only connect when disconnected from the mains pow-
er supply! Switch off power supply and secure against
reconnection!
!
!
Cable installation must be in compliance with applicab-
le legal requirements. The terminal cross section for the
rain sensor must be minimum 1,5 mm², for the wind sen-
sor minimum 0,5 mm².
In case of fire (EMERGENCY-OPEN) or failure of power supply (accu-
mulator operation) the ventilation control via wind and rain sensors is
deactivated.
Before mounting and positioning the wind/rain sen-
sors carefully read the safety and assembly instructions
provided with the products. They are part of the system
documentation and must be adhered to and kept accor-
dingly (e.g. for servicing purposes).
I
nstAllAtIon
step
4:
C
onnECting
Wind
And
RAin
sEnsoRs
2,5 A
5 A
20 A
10 A
I
nstAllAtIon
step
4:
C
onneCting
W
inD
anD
r
ain
s
ensors
04
USB
1 22
1 13 14 15 16 17 18 19
A
S
B
-
-
-
+
1
1
1
22
5
71
1 13 14 15 16 17 18 19
A
S
B
1 72
-
-
-
+
1
1
5
71
1 72
24 V
1 2 3 4 5
24 V
1 2 3 4 5
-
+
not used
not used
max. 200 m
min. 1,5 mm
2
max. 200 m
min. 1,5 mm
2
max. 200 m
min. 0,5 mm
2
Control indicators:
Rain active:
(GN) = on
(YE) =
2 x
blinking
(RD) = off
Wind active:
(GN) = on
(YE) =
3 x
blinking
(RD) = off
Wind & Rain active:
(GN) = on
(YE) =
4 x
blinking
(RD) = off
A
S
B
A
S
B
A
S
B
Connection
Wind / Rain
Sensor for:
Rain sensor
Rain sensor
Wind sensor
Wind sensor
Juncion
box
Sensor for:
Rain
Rain
Wind
Wind
or
Breakglass unit
Breakglass unit
SD
SD