17
Installation instruction
RWA - Control Unit EMB 7300
I
nstAllAtIon
step
6:
C
onneCting
P
oWer
s
uPPly
I
nstAllAtIon
step
6:
C
onnECting
poWER
sUpply
1 32 33 35 36 37
+
+
+
+
-
∼
∼
N L
1
1
1
1
22
5
71
72
1 13 14 15 16 17 18 19
A
S
B
1 2 3
F1
US
B
A
Z
Reset
A
Z
A-
A+
F2
F3
A-
-
-
US
B
The system software includes the option to activate the
automatic closing feature in the event of a power failure
(standard = „no“).
USB
05
Connecting power supply: Version EMB 7300
2,5A
-0101, EMB 7300
2,5A
-0101-T
PE
Switch
accumulators
in series
Route line voltage supply via external fuse and
switching component. Only connect supply voltage
and accumulator set when disconnected from the mains
power supply! Switch off power supply and secure
against reconnection!
Cover
RD
RD
RD
L
Cover
SMOKE VENT
N
225 mm
285 mm
230V AC
50 - 60 Hz
On the version with front-mounted
push button the connector may be
removed!
Routing via external fuse and
switching component!
PE
BU
BU
BU
2 x back-up accumulator 2,3 Ah 12V
!
!
Ensure correct polarity when connecting!
!
= red
= blue
Attachment of the accumulators with the
optional accumulator holder set (Part.-No.:
683250)
only for compact housing
The accumulator set may also be fastened to the housing with the
optional accumulator holder set.
!
It is essential to ensure correct polarity when connecting
the accumulator set! Incorrectly connected accumulators
will cause damage to the controller!
Mounting the accumulator holder set:
Press 2 x (right and left) plastic screw-plug
into the squares on
the rear side of the housing.
Fasten bracket
with screw
in screw-plug
on the right and
on the left.
2x
Back-up accumulators
Accumulator holder set
Part.-No.:
Material:
Colour:
683250
Steel
RAL 9016 (white)
Suitable for:
EMB 7300
EMB 7300
2,5 A
5 A
2,5 A
5 A
2,5 A
2,5 A
5 A
20 A
10 A