14
Installation instruction
RWA - Control Unit EMB 7300
I
nstAllAtIon
step
3:
C
onneCting
s
moke
D
eteCtors
anD
b
reakglass
u
nits
Connection of automatic and manual smoke detectors / BMZ
Instead of smoke detectors a connection module
(external closer contact) for EMERGENCY-OPEN from an
external fire alarm system (FAS) may be connected to
terminal 1 / 22.
Only connect when disconnected from the mains pow-
er supply! Switch off power supply and secure against
reconnection!
!
!
Cable installation must be in compliance with applica-
ble legal requirements. The terminal cross section for
connecting the detectors is maximum 1,5 mm², mini-
mum 0,5 mm².
The fire detector connection is closed-circuit monitored
for line failures. Therefore, both the last smoke detector
and the last breakglass unit in the line must be provided
with a 10 k
Ω
resistor (RE) (see schematic diagram). If
the fire alarm line is not used, mount the 10 k
Ω
resistor
on terminal 1 / 22. Otherwise, the yellow indicator „
S
“
signals a fault
I
nstAllAtIon
step
3:
C
onnECtion
of
AUtoMAtiC
And
MAnUAl
sMokE
dEtECtoRs
04
OK
11
10
9
8
7
6
5
4
3
2
1
1
1
1
22
5
71
1 13 14 15 16 17 18 19
A
S
B
1 72
OK
11
10
9
8
7
6
5
4
3
2
1
+
+
+
+
-
+
10 k
+
IN
CO
M
OUT
IN
CO
M
OUT
IN
CO
M
OU
T
BMA
1 2 3 4 5
1
22
1
22
COM-
OUT+
IN+
IN+
IN+
OUT+
OUT+
COM-
COM-
R
E
1
13
14
15
16
18 19
1 2 3 4 5 6 7 8 9 10 11
2,5 A
5 A
20 A
10 A
Automatic smoke detector
Breakglass unit
Buttons Indicators
COM
Indicators
max. 0,1 A
max. 10 units
max. 400 m
Breakglass unit
Cable length
max. 400 m
Terminal
EMB 7300
Terminals
EMB 7300
Line monitoring up to
the connection module.
Signal processing can
be configured with
licensed software.
External
fire alarm system
Terminal
EMB 7300
or
USB
remove
RE
Do not remove
RE
in the last
breakglass unit of the line!
If neither smoke detectors or a
fire alarm system module are connected,
install a 10 k
Ω
resistor between terminal 1 / 22.
Install
RE
in the last
detector of the line!
CLOSE
E-OPEN
E-OPEN
Operation
Fault
!
!
!
!
!
!
!
!
Connectionmo-
dul
Buttons
Indicators
EMERGENCY
-
OPEN
EMERGENCY
-
CLOSE
EMERGENCY
-
OPEN
RD
GN
YE
OK
= not with breakglass unit N
(N = secondary control device)
(Built-in BMZ)
BMZ
If terminals 1/13/14/15/16/17/18/19
are not occupied, install a 10 k
Ω
resistor
between terminal 1 / 13.
!