7.6.8 Input range of setpoint 1: view/edit
The parameters of this setting depend on the pre-set setpoint source
(
SETPOINT E1 (M4100)
parameter, page 54).
Initial and end value via the Foundation Fieldbus interface
In Foundation Fieldbus standard version, the setpoint E1 is transmitted via
the AO function block.
Initial and end value via I/O interface
As an option, the setpoint E1 can be supplied via an analogue input instead
of using the fieldbus. This is possible for the following versions:
a) in addition to the Foundation Fieldbus interface, the AUMATIC is equip-
ped with a further parallel interface (refer to page 66)
b) the AUMATIC is equipped with additional control inputs (refer to page 63)
The input range amounts to 0/4 – 20 mA. It is possible to modify the input
range via the display for both versions:
Version a) for setpoint source of parallel interface, analogue input 1:
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
I/O ANLOG IN1 START (M410H)
I/O ANLOG IN1 END (M410I)
Default values:
I/O ANLOG IN1 START
=
0
m
A
I/O ANLOG IN1 END
=
20
m
A
Setting ranges:
I/O ANLOG IN1 START
=
0
to
20
m
A
I/O ANLOG IN1 END
=
0
to
20
m
A
Version b) for setpoint source of Foundation Fieldbus interface,
analogue input 1:
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
FF-INTERFACE 1 (M1M)
FF ANLOG IN1 START (M1M00)
FF ANLOG IN1 END (M1M01)
Default values:
FF ANLOG IN1 START
=
0
m
A
FF ANLOG IN1 END
=
20
m
A
Setting ranges:
FF ANLOG IN1 START
=
0
to
20
m
A
FF ANLOG IN1 END
=
0
to
20
m
A
Information
If the measuring values are 0.3 mA below the initial value a wire break is
indicated as a warning.
55
Actuator controls
Manual
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
VIEW
I/O1 ANLOG IN1 END
20 mA
C:ESC
VIEW
I/O1 ANLOG IN1 START
0.0 mA
C:ESC
VIEW
FF ANLOG IN1 END
20.0 mA
C:ESC
VIEW
FF ANLOG IN1 START
0.0 mA
C:ESC