6.3
Operation mode REMOTE
Ò
Set selector switch to position Remote control (REMOTE).
Display indicates:
The actuator is controlled by external REMOTE commands OPEN - STOP -
CLOSE.
Information
If SETPOINT MODE is displayed, a positioner (option) is available. In this
case, selection can be made between REMOTE MODE and SETPOINT
MODE (refer to page 53).
6.3.1 Push-to-run operation or self-retaining: set for operation mode REMOTE
The parameter has no influence on the operation commands transmitted via
fieldbus.
Setting is only required if a further parallel interface is available in addition to
the fieldbus interface (refer to page 66).
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
I/O 1 (M14)
MAINTAINED REMOTE (M1410)
Default value:
OFF
È
Description of the parameter settings:
OFF
Push-to-run operation off, self-retaining activated:
Actuator runs in direction OPEN or CLOSE after an operation command has
been issued. If the operation command is removed, the actuator continues
to run (self-retaining) until it is stopped by the STOP command or an end
position or intermediate position has been reached.
OPEN
Push-to-run operation in direction OPEN activated:
Actuator only runs in direction OPEN while an operation command is
issued. If the operation command is removed, the actuator stops.
CLOSE
Push-to-run operation in direction CLOSE activated:
Actuator only runs in direction CLOSE while an operation command is
issued. If the operation command is removed, the actuator stops.
OPEN + CLOSE (STOP)
Push-to-run operation in direction OPEN and CLOSE activated:
33
Actuator controls
Manual
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
REMOTE MODE
S0
0
I
I
EDIT
M1410
MAINTAINED REMOTE
OFF
:EDIT
↵
:OK
C:ESC