4.4.3 Blinking behaviour of indication lights/LEDs: view/edit
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
LOCAL CONTROLS (M13)
BLINKER (M1311)
Default value:
OFF IN MIDPOSITION
È
Description of the parameter settings:
OFF
Blinker is switched off.
LIT IN MIDPOSITION
OFF IN MIDPOSITION
Information
The
BLINKER
parameter also influences the blinking behaviour of output
contacts 1 to 5 if they are used as a running indication.
21
Actuator controls
Manual
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
LED 1 only (yellow)
illuminated
Actuator is in end position CLOSED
LED 1 (yellow)
blinking
Actuator runs in direction CLOSE (running
indication)
LED 5 only (green)
illuminated
Actuator is in end position OPEN
LED 5 (green)
blinking
Actuator runs in direction OPEN (running in-
dication)
Table 6
EDIT
M1311
BLINKER
OFF IN MIDPOSITION
:EDIT
↵
:OK
C:ESC
LED 1 (yellow)
illuminated
Actuator is in end position CLOSED
blinking
Actuator runs in direction CLOSE (running
indication)
LED 5 (green)
illuminated
Actuator is in end position OPEN
blinking
Actuator runs in direction OPEN (running in-
dication)
Table 7