Information
For actuators equipped with positioner, it is possible to optionally select between
open-close duty (REMOTE OPEN-CLOSE) and modulating duty (REMOTE
SETPOINT). Selection is made via REMOTE MANUAL input, e.g. based on a 24 V
DC signal (refer to wiring diagram).
Behaviour in modulating duty for version with positioner:
In case of signal loss of setpoint E1 or actual value E2, the actuator moves to a
preset position. The following reactions are possible:
●
Fail as is: Actuator stops immediately and remains in this position.
●
Fail close: Actuator moves the valve to end position CLOSED.
●
Fail open: Actuator moves the valve to end position OPEN.
The behaviour on loss of signal can be set via a switch in the controls.
27
SQEx 05.2 – SQEx 14.2 / SQREx 05.2 – SQREx 14.2
AMExC 01.1
Operation
Summary of Contents for AMExC 01.1
Page 70: ...15 2 ATEX certificate 70 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 Certificates AMExC 01 1...
Page 71: ...71 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1 Certificates...
Page 72: ...72 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 Certificates AMExC 01 1...
Page 73: ...73 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1 Certificates...
Page 74: ...74 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1...
Page 75: ...75 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1...