II.1.3 CHECKING THE INSTALLATION
In checking the suitability of the electrical installation in which the CCR is to be integrated, the following
points must be observed:
II.1.3.1 Single phase power supply:
This must be compatible with the electrical characteristics of the device as shown on the rating plate and
factory test report.
The rated mains voltage is recorded in the software on the motherboard and is required for calculations.
The configured rated voltage can be seen in the “Configuration” menu, and written on the identification
plate, on the front panel.
L
See paragraph I.3.3 for the electrical characteristics of DIAM CCRs.
II.1.3.2 LV Protection:
The LV protection for each CCR from the mains must be proportioned according to the power of the CCR,
the rated voltage and the type of protection already present on the CCR.
The following tables are given for information only, for cable lengths between fuse boxes and CCRs of less than
30m (Circuit breaker examples : MG references)
380 to 415V Power Supply
208 to 277V Power Supply
Power
LV cable gauge
LV circuit breaker
LV cable gauge
LV circuit breaker
2,5 kVA
4 mm²
C60N 16A B
6 mm²
C60N 20A B
4 kVA
6 mm²
C60N 25A B
10 mm²
C60N 40A B
5 kVA
6 mm²
C60N 25A B
10 mm²
C60N 40A B
7,5 kVA
10 mm²
C60N 40A B
16 mm²
C60N 63A B
10 kVA
16 mm²
C60N 50A B
16 mm²
NC100H 80A B
15 kVA
16 mm²
NC100H 80A B
25 mm²
NS100N TM100D
20 kVA
25 mm²
NC100H 100A B
35 mm²
NS160N TM125D
25 kVA
25 mm²
NS100N TM100D
50 mm²
NS160N TM160D
30 kVA
35 mm²
NS160N TM125D
70 mm²
NS250N TM200D
II.1.3.3 Lighting loop:
Check that the installed power corresponds to the power of the CCR, check the continuity of the loop and
the number of lamps blown.
The rated output power is recorded in the software on the motherboard and is required for calculations.
The configured rated power can be seen in the “Configuration” menu
II.1.3.4 Management by remote control:
Check the remote control mode: dry contact/external voltage/serial network. For external voltage mode
(multiwire interface), check that the remote control voltage is compatible with the electrical characteristics of the
CCRs.
L
See paragraph I.3.3 for the electrical characteristics of the DIAM CCRs.
L
See paragraph II.3 in order to configure the remote control mode.