©2004 AUGIER SA.
I-20
I.5.1 CONFIGURATION
The “Configuration” menu is used to define the basic parameters of the CCR (for example when replacing the
main board):
•
Rated mains voltage in Vrms: 208-220-230-240-277-380-400-415-480
•
Rated power in KVA:1-2.5-4-5-7.5-10-15-20-25-30
•
Number of brightness (Including B0): from 1 to 8
•
Mains frequency in Hz: 50 or 60
•
FAA or IEC type
I.5.2 SETTING
The “Setting” menu is used to assign values of current to brightness levels B0 to B7.
•
Minimum value = 1Arms
•
Maximum value = 6.8Arms
I.5.2.1 Current
range:
The “Regulation Error” warning is triggered if the measured current is outside the ranges defined for each
setting B0 to B7.
Each range is automatically calculated when a setting is changed (as described below) in the following way:
•
Minimum value = Setting – 3%
•
Maximum value = S3%
Nevertheless it is possible to set two limits of the current range manually using the “Current range” menu.
I.5.3 PROTECTIONS
I.5.3.1 LV power monitoring:
Mains voltage
Duration CCR status
Ui < 75% of rated voltage
0s
CCR stops (Power supply Warning)
Ui > 130% of rated voltage
0s
CCR stops (Power supply warning)
Ui < 85% of rated voltage
60s
CCR stops (Power supply warning)
Ui > 120% of rated voltage
60s
CCR stops (Power supply warning)
90% < Ui < 110% of rated voltage
0s
CCR automatically restarts
I.5.3.2 “Open circuit”:
Open Circuit Protection is activated if the output current goes below a defined value (I level OC) for a
defined period (Duration OC). The CCR stops instantly, and the display shows the message “Open Circuit”.
Setting I level OC and Duration OC:
Go into the menu “Alarms and Warnings” then “Open Circuit”.