Hardware Installation Manual
4. Cabling
Version 7.0
23
Mediant 9000 SBC
Caution:
To reduce the risk of electric shock or damage to the equipment:
•
Do not disable the power cord grounding plug. The grounding plug is an important
safety feature.
•
Plug the power cord into a grounded (earthed) electrical outlet that is easily accessible
at all times.
•
Unplug the power cord from the power supply to disconnect power to the equipment.
•
Do not route the power cord where it can be walked on or pinched by items placed
against it. Pay particular attention to the plug, electrical outlet, and the point where the
cord extends from the server.
Note:
•
This equipment is intended for installation where the NEC (National Electrical
Code) applies.
•
The safety ground of the AC power cord must terminate the chassis to the interior
equipment grounding system.
To connect the device to the AC power supply:
1.
Connect the AC power cord (supplied) to one of the power sockets located on the rear
panel.
Figure
4-1: Connecting AC Power Cords to AC Electrical Outlets
2.
Connect the other end of the power cord to a standard AC electrical outlet (100-
240V~50-60 Hz).
3.
For load sharing and power redundancy, repeat steps 1 through 2, but using the
power socket of the second Power Supply module and connecting this to a different
supply circuit.
4.
Turn on the power at the power source (if required).
5.
Check that the
POWER
LED on each Power Supply module (front panel) is lit green.
This indicates that the device is receiving power.